May 2016
Reference Manual
00809-0100-4530, Rev DD
286
B.2 European Directive information
The most recent revision of the EC declaration of
conformity can be found at
.
B.3 Safety Instrumented Systems
(SIS)
SIL 3 Capable: IEC 61508 certified by an accredited 3rd
party agency for use in safety instrumented systems up to
SIL 3 (Minimum requirement of single use (1oo1) for SIL 2
and redundant use (1oo2) for SIL 3).
For more information, go to:
EmersonProcess.com/Rosemount-Safety
B.4 Hazardous locations
certifications
Other temperature restrictions may apply beside the ones
mentioned in the following sections. For more information,
see
“Process temperature and pressure rating” on
.
B.4.1 North-American certifications
Factory Mutual (FM) approvals
Project ID: 3020497
E5
Explosion-proof:
Explosionproof-Intrinsically Safe for Class I, Division 1,
Groups B, C and D.
Dust-ignition-proof for Class II/III, Division 1, Groups
E, F, and G with intrinsically safe connections to Class I,
II, III, Div 1, Groups B, C, D, E, F, and G.
Temperature code T4.
Ambient temperature limits: -50
°
C to + 70
°
C
(1)
.
Seal not required.
Approval valid for the HART
®
, F
OUNDATION
™
Fieldbus,
and Modbus
®
options.
I5, IE
Intrinsically Safe, Non-Incendive, and FISCO model:
Intrinsically Safe for Class I, II, III, Division 1, Groups A,
B, C, D, E, F, and G.
Class I, Zone 0, AEX ia IIC T4 when installed per control
drawing: 9240 030-936.
Non-incendive for Class I, II, Division 2, Groups A, B, C,
D, F, and G. Suitable for Class III, Division 2;
4-20 mA/HART model: U
i
= 30 Vdc, I
i
= 130 mA,
P
i
= 1.0 W, C
i
= 7.26 nF, L
i
= 0
H.
Max operation 42.4 V, 25 mA.
F
OUNDATION
Fieldbus model: U
i
= 30 Vdc, I
i
= 300 mA,
P
i
= 1.3 W, C
i
= 0 nF, L
i
= 0
H.
Max operation 32 V, 25 mA.
FISCO model: U
i
= 17.5 Vdc, I
i
= 380 mA, P
i
= 5.32 W,
L
i
= C
i
= 0.
Temperature code T4.
Ambient temperature Limits: -50
°
C to + 70
°
C
Approval valid for HART, F
OUNDATION
Fieldbus, and
FISCO options.
Special Conditions of Use:
WARNING: Potential Electrostatic Charging Hazard – The
enclosure is constructed from a non-metallic material. To
prevent the risk of electrostatic sparking the plastic surface
should only be cleaned with a damp cloth.
WARNING: The apparatus enclosure contains aluminum
and is considered to constitute a potential risk of ignition by
impact or friction. Care must be taken into account during
installation and use to prevent impact or friction.
1.
+60 °C with F
OUNDATION
Fieldbus or FISCO option.