![Rosemount 5300 Series Reference Manual Download Page 209](http://html1.mh-extra.com/html/rosemount/5300-series/5300-series_reference-manual_1487396209.webp)
195
Reference Manual
00809-0100-4530, Rev DD
May 2016
7.25
F
OUNDATION
Fieldbus error messages
7.25.1
Resource block
This section describes error conditions found in the Resource block. Read
through
to determine the appropriate corrective action.
Block errors
lists conditions reported in the BLOCK_ERR parameter.
Table 7-13. Resource Block BLOCK_ERR Messages
Table 7-14. Resource Block SUMMARY_STATUS Messages
Condition name and description
Other
Simulate Active:
This indicates that the simulation switch is in place.
This is not an indication that the I/O blocks are using simulated data
Device Fault State Set
Device Needs Maintenance Soon
Memory Failure:
A memory failure has occurred in FLASH, RAM, or EEPROM memory
Lost Static Data:
Static data that is stored in non-volatile memory has been lost
Lost NV Data:
Non-volatile data that is stored in non-volatile memory has been lost
Device Needs Maintenance Now
Out of Service:
The actual mode is out of service
Condition name
Uninitialized
No repair needed
Repairable
Call Service Center