Volume calculation status
Volume calculation status messages that may appear on the Integral Display, on the Field
Communicator, or in RRM are shown in
:
Table 7-9. Volume Status
Message
Description
Action
Level is below lowest
strapping point.
The measured level is below the lowest point
in the given strapping table.
For a correct volume calculation in this
region, change the strapping table.
Level is above highest
strapping point.
The measured level is above the highest point
in the given strapping table.
For a correct volume calculation in this
region, change the strapping table.
Level out of range.
The measured level is outside the given tank
shape.
Check if the correct tank type is chosen
and check the configured Tank Height.
Strap table length not valid.
The configured strap table length is too small
or too large.
Change the strapping table size to a valid
number of strapping points. A maximum
number of 20 strapping points can be
entered.
Strap table not valid.
The strapping table is not correctly
configured.
Check that both level and volume values
in the strapping table are increasing with
strapping table index.
Level not valid.
The measured level is not valid. No volume
value can be calculated.
Check Measurement Status, Warning and
Error Messages.
Volume configuration
missing.
No volume calculation method is chosen.
Do a volume configuration.
Volume not valid.
The calculated volume is not valid.
Check the other volume status messages
for the reason.