INSTALLATION
PROCEDURE
Specific installation procedures use Siemens’ PDM Configuration tool as a
reference. For other configuration tools, use that products reference manual.
All devices are shipped with a default address of 126.
Profibus Device
Description and GSD File
Use the following steps to install the Profibus Device Description and
GSD file.
1.
Go to the Rosemount web site, located at
<http://www.rosemount.com/products/temperature/m3244pa.html>.
2.
Download the Rosemount 3244 DD zip file.
3.
Read the “read me” file on how to install DDs and GSD files.
(It is important to read this file because it is unique to each
Profibus- PA interface tool.)
4.
Click the “Next” button when the program begins.
5.
Provide the path “c:\Temp\3244MVM.devices at the appropriate
prompt.
6.
Select “Search in” and click Next
7.
Indicate the device where the DD is to be installed (in this case select
3244MVM(PA).
8.
Click “Finish.”
9.
Close the application when installation is completed.
Changing the Mode of
a Block
Use the following steps to change the mode of a block.
1.
Select “Device Mode,” located under the “Device” pull-down menu.
2.
Choose “Out of Service (O/S)” to change parameter settings.
3.
Indicate the mode desired for the block and press the
download button.
4.
Select the “Load into PG/PG” option, located under the “Device”
pull-down menu.
5.
Upon completion, the block will be in the mode set.
NOTE
Changing the mode of one transducer block changes all the transducer blocks
to that same mode.
Summary of Contents for 3244MV
Page 2: ......
Page 4: ......
Page 46: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV A 12 ...
Page 58: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV B 12 ...
Page 60: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV Index 2 ...
Page 61: ......