background image

Rosemount Nuclear Instruments, Inc.

3

Qualified Life

Qualified life is dependent on continuous ambient 

temperature at the installation site (see Figure 1) 
as well as the number of functional cycles. See 
Rosemount Qualification Report D8200037 for 
more detail regarding qualified life. 

FIGURE 2. Model 710DU Trip/Calibration System Diagram.

7

1

0

-0

5

8

1

A

24 V

POWER 

SUPPLY

Calibrate 
Command

Calibration 
Current

Calibration Status Test 
Jack

Trip Status

Auxiliary Analog 
Output Test Jack

Gross Failure Output

Trip Output

Test Jack Sensor Signal

3-WIRE 100 

PLATINUM 

RTD

4–20 mA 

PRESSURE 

TRANSMITTER

CALIBRATION 

UNIT WITH 

READOUT 

ASSEMBLY

RTD INPUT 

MASTER TRIP 

UNIT 

(1 REQUIRED 

FOR EACH 

RTD)

4–20 mA 

INPUT 

MASTER 

TRIP UNIT

SLAVE 

TRIP 
UNIT

Trip Status

Trip Status

Sensor Signal Test Jack

Gross Failure Output

Trip Output

Slave Input Test Jack

Gross Failure Output

Trip Output

Auxiliary Analog Output 
Test Jack

Trip Status

Signal from

Selected

Master or Slave

Trip Unit

Calibration

Current

Calibrate

Command

To Additional 
Master or 
Slave Trip 
Units

To Additional Slave Trip Units 
(7 Maximum per Master Trip Unit)

Card File

1–5 V dc Auxiliary Analog 
Output

Calibrate

Command

Calibration

Current

FIGURE 1. Qualified Life vs. Temperature.

Qualified Life

7

1

0

-0

3

0

8

A

Temperature (°F)

T

im

e

 (

Y

e

a

rs

)

Summary of Contents for 710DU

Page 1: ...00813 0100 4471 English May 1999 Rev AB Model 710DU Trip Calibration System ...

Page 2: ... proportional controller or recorder The trip point circuit features precision external adjustment with either high or low nonlatching trip action The gross failure circuits are internally adjustable with manual reset high and low trip action Trip point and gross failure indicating lamps are furnished on each trip unit Calibration Unit The trip point for any master or slave trip unit within the ca...

Page 3: ...3 WIRE 100 V PLATINUM RTD 4 20 mA PRESSURE TRANSMITTER CALIBRATION UNIT WITH READOUT ASSEMBLY RTD INPUT MASTER TRIP UNIT 1 REQUIRED FOR EACH RTD 4 20 mA INPUT MASTER TRIP UNIT SLAVE TRIP UNIT Trip Status Trip Status Sensor Signal Test Jack Gross Failure Output Trip Output Slave Input Test Jack Gross Failure Output Trip Output Auxiliary Analog Output Test Jack Trip Status Signal from Selected Maste...

Page 4: ...drive independent external relays Test jacks are also provided for monitoring the sensor input and auxiliary analog output signal Slave Trip Units Each slave trip unit adds one additional trip output circuit and one gross failure output circuit to any transmitter loop with a master trip unit It has the same features as a master trip unit except that it has no meter and no analog output FIGURE 3 Ma...

Page 5: ...libration current to any master trip unit channel while reading the trip point of the master or its associated slaves A calibration status signal for remote display and a lamp on the faceplate indicate that the system is in the calibration mode Test jacks are provided to monitor the time response of the user s system Readout Assembly The digital readout assembly displays both calibration and trip ...

Page 6: ...l film potentiometer on circuit card RTD master trip unit only Linearity Single turn potentiometer on circuit card RTD master trip unit only Indicator LEDs Trip status and gross failure LED on faceplate Test Jacks Signal input and auxiliary analog output voltages may be read with external meters on master trip units and slave input signal on slave trip units Calibration Unit Adjustment and Control...

Page 7: ...rips on the rear of the card file Screw terminals are sized for 6 spade lugs Analog Indication Master trip units have 13 4 in vertical meters scaled in appropriate engineering units Paint Flat black with white letters baked enamel paint CARD FILE The 710DU system card file is designed to accommodate one plug in calibration unit plus any combination of up to 12 interchangeable plug in master and sl...

Page 8: ...sembly Description TT TR TS Master Trip Unit 4 20 mA Input Master Trip Unit RTD Input Slave Trip Unit Code Meter Option XXXXX Assigned by Rosemount for each Meter Scale Used on TT and TR Assemblies Only Typical Model Number 710DU 0 TR 74024 Model Product Description 710DU0 Trip Calibration System for Nuclear Applications Code Assembly Description CF CL RA1 BT BC B1 B2 ET EC ER Card File Calibratio...

Reviews: