RESISTRON

RESM-4/RESM-5 

Replacement

GB

Replacement

instruction

The RESM-5 monitoring unit can be used as an
alternative to the RESM-4.
The steps necessary to convert from RESM-4 to
RESM-5 are described below.
These instructions provide only a brief overview of the
two monitoring units. If in doubt, please refer to the
latest version of the monitoring unit documentation,
which is always binding.
The electrical connections of the RESM-4 and RESM-5
monitoring units are NOT compatible (see wiring
diagrams).

The two models are also operated differently. Whereas
potentiometers are used to calibrate the RESM-4 and
set the alarm threshold, you do this on the RESM-5 with
a display and four keys.

Older RESM-1 monitoring units (for
temperature controllers in the "2xx" series)

cannot be converted using the RESM-5. 

Preparation

1.

Select the unit

Select an RESM-5 with the same line voltage as the
old RESM-4 monitoring unit (115VAC, 230VAC, or
400VAC). The RESM-5 monitoring unit has the
following order numbers:

Line voltage:

115VAC 

 RESM-5/115VAC

Art. No. 885241

230VAC 

RESM-5/230VAC
Art. No. 885242

400VAC 

RESM-5/400VAC
Art. No. 885243

The line frequency is automatically detected
by the RESM-5 monitoring unit in the range
from 47 to 63Hz.

2.

Select the required components

Trouble-free operation of the RESM-5 monitoring
unit is only guaranteed in combination with the
following components:
- PEX-W2 or PEX-W3: Current transformer
- Alternatively: MSW-1 or MSW-2:

Monitoring current transformer

- LF-06480: Line filter 6A, 480VAC

In order to avoid malfunctions, the RESM-5 is
only allowed to be operated with the

specified components.

!

!

Summary of Contents for RESISTRON RESM-4

Page 1: ... 4 and set the alarm threshold you do this on the RESM 5 with a display and four keys Older RESM 1 monitoring units for temperature controllers in the 2xx series cannot be converted using the RESM 5 Preparation 1 Select the unit Select an RESM 5 with the same line voltage as the old RESM 4 monitoring unit 115VAC 230VAC or 400VAC The RESM 5 monitoring unit has the following order numbers Line volta...

Page 2: ...un AUTOCAL Old setting ranges on the RESM 4 AUTORANGE function on the RESM 5 The RESM 5 monitoring unit has no coding switches on the housing The voltage 0 4 120V and current 30 500A ranges are automatically set when you run the AUTOCAL function Heed the information provided in the ROPEX Application Report in order to avoid malfunctions 4 The number of times the wire is laid through the PEX W2 3 o...

Page 3: ... higher level controller You should therefore only use this function if the risk analysis for the machine or plant allows To calibrate the zero point AUTOCAL on the RESM 5 Run the AUTOCAL function while the heatsealing band is cold Press the key repeatedly until menu step 107 is displayed Then select the AUTOCAL function by pressing the key If this function is executed correctly the main menu is a...

Page 4: ...u is not changed when you restore the factory settings As shipped condition The RESM 5 monitoring unit is shipped with the above factory settings and with the language set to German Menu Function Value 107 AUTOCAL temperature 20 C 204 Alloy 400ppm K 205 Range 300 C 206 Maximum temperature alarm threshold 40 C 213 Key lock No key 215 Alarm output Normal energized at alarm 225 Temperature unit Celsi...

Page 5: ...tion Power up message 208 Set point exceeded 206 Max temperature 210 Cooling mode 212 Relay K1 function 213 Key lock 207 Set point reached 205 Temperature range Setting Configuration 211 Heatslg time start Error 215 Alarm output 204 Temp coefficient 214 Cycles 107 Autocal 102 Preheat temp Autocal 5 6 209 Time control 1 2 216 Analog output 1 2 217 Temp diagnosis 218 Temp diag delay Continued on nex...

Page 6: ...lacement 221 Autocomp 220 Meas imp length 219 Heatup timeout Configuration 222 Output 1 Continued from previous page Back to home position 225 Temperature unit 226 System time 227 Visualization 228 Screensaver 229 RESET input ...

Page 7: ...rim U1 Twisted Auxilary power supply ANALOG OUTPUT actual value 0 10VDC 0V Internal ground NO EXTERNAL GROUNDIG ALLOWED Current transformer PEX W2 W3 11 10 IR NC NC NC NC 1 2 7 8 8 7 5 6 X Terminals on RESM 4 See RESM 5 documentation See RESM 5 documentation Note If error code 118 appears when you switch on the RESM 5 these cables should be reversed interchanged 9 10 11 or 12 13 14 or 15 Ground Mu...

Page 8: ... coil HEATSEALING BAND Or from MAIN CONTROLLER RES UR CONTACT CONTACT LOGIC SIGNAL or 24VDC 0V signal 5 6 7 8 2 1 Twisted LINE 13 NO 12 9 11 10 14 NC 15 C ALARM OUTPUT RELAY max 100VDC 240VAC 1 5A ALARM INPUT FROM MAIN CONTROLLER ALARM OUTPUT RES MAIN CONTROLLER RESM 4 Relay energized in go state 0 24V In phase with RES controller ...

Reviews: