Technical data
Version 1
RES-402
Page 29
9
Technical data
Type of construction
Housing for installation in the electrical cabinet
Snaps onto a standard top hat rail (DIN TS35 rail, 35mm) acc. to DIN EN 50022
Dimensions: 90 x 75mm; height: 135mm (incl. terminals)
Line voltage
All controllers manufactured as of January 2006:
115VAC version: 110VAC -15%…10% (equivalent to 94…132VAC)
230VAC version: 220VAC -15%…10% (equivalent to 187…264VAC)
400VAC version: 380VAC -15%…10% (equivalent to 323…456VAC)
All controllers manufactured up to December 2005:
115VAC version: 115VAC -15%…10% (equivalent to 98…132VAC)
230VAC version: 230VAC -15%…10% (equivalent to 196…264VAC)
400VAC version: 400VAC -15%…10% (equivalent to 340…456VAC)
Depending on the controller version (
section 12 "How to order" on page 31)
Line frequency
47…63Hz, automatic adjustment to frequencies in this range
Auxiliary voltage
Terminals 14+13
24VDC, +20%, -10%, reverse polarity-protected
Current input: max. 1.0A
Heatsealing band
type and temperature
range
Default value 300°C, Alloy A20
Analog input
(set point)
Terminals 15+12
0…10VDC, I
max
= 5mA, electrically isolated
Equivalent to 0…300°C
or with an external PD-3 precision potentiometer (R = 2kohms)
0…2kohms equivalent to 0…300°C
Analog output
(actual value)
Terminals 11+12
0…10VDC, I
max
= 5mA, electrically isolated
Equivalent to 0…300°C
Accuracy: ±1% add. 50mV
Reference voltage
+10VDC / ±5%, I
max
= 5mA
Digital logic levels
Terminals 16, 17, 18
LOW (0V): 0…2VDC, electrically isolated
HIGH (24VDC): 12…30VDC (max. current input 6mA)
Reverse polarity-protected
Alarm output
U
ON
< 3V (saturation voltage), I
max
= 200mA, electrically isolated,
short-circuit proof
Maximum load
(primary current of
impulse transformer)
I
max
= 5A (duty cycle = 100%)
I
max
= 25A (duty cycle = 20%)
Power dissipation
max. 20W
Ambient
temperature
+5…+45°C
Degree of protection
IP20