background image

INTRODUCTION

Your bar shower valve is a thermostatic mixer which incorporates a thermo-regulating cartridge to assure users of 

consistent showering temperatures. The valve has been designed & manufactured to comply with BS EN 1287:1999 & 

BS EN 1111:1999.

OPERATING CONDITIONS OF USE

Before installation the operating conditions of use must be checked.  The table below contains details of the necessary 

conditions of operation.  If your water supply cannot meet these conditions then the valve cannot be guaranteed to 

operate as a Type 2 TMV2 certified shower valve.  This valve is suitable for use in both low pressure (BS 1287) and high 

pressure (BS 1111) operating conditions with the following systems:

•  Gravity fed Hot & Cold (equal pressures)

•  Gravity fed Hot & mains Cold (differential pressure – max ratio 3:1)

•  Unvented systems

•  Gas combination boiler

•  Pumped system

Note: On gravity systems the minimum Vertical distance (Drop) from the underside of the cold water storage tank to the 

shower valve must be 3 metres.

CONDITIONS OF USE FOR TYPE 2 VALVES

NOTE:

 

Valves operating outside these conditions cannot be guaranteed by the Scheme to operate as Type 2 valves.

Recommended outlet temperatures

The BuildCert TMV scheme recommends the following set maximum mixed water outlet temperatures for use in all 

premises:

41°C for showers;

The mixed water temperatures must never exceed 46°C.

The maximum mixed water temperature can be 2°C above the recommended maximum set outlet temperatures.  

NOTE:

46°C is the maximum mixed water temperature from the bath tap.  The maximum temperature takes account of the 

allowable temperature tolerances inherent in thermostatic mixing valves and temperature losses in metal baths.

It is not a safe bathing temperature for adults or children.

The British Burns Association recommends 37 to 37.5°C as a comfortable bathing temperature for children.  In premises 

covered by the Care Standards Act 2000, the maximum mixed water outlet temperature is 43°C.

The thermostatic mixing valve will be installed in such a position that maintenance of the TMV and its valves and the 

commissioning and testing of the TMV can be undertaken.

The fitting of strainers is recommended as close as is practicable to the water supply inlets of the thermostatic mixing 

valve.

HIGH PRESSURE

LOW PRESSURE

Maximum Static Pressure - BAR
Flow Pressure, Hot & Cold - BAR
Hot Supply Temperature - °C
Cold Supply Temperature - °C

10

0.5 to 5

55 to 65

Equal to or less than 25°C

10

0.1 to 1

55 to 65

Equal to or less than 25°C

TROUBLE-SHOOTING

If you require further assistance beyond the guide below contact the help line on  01225 303 900

AFTERCARE INSTRUCTIONS

Whilst this item has a high quality durable finish, it should nevertheless be treated with care.  Surfaces should be 

cleaned using only a soft damp cloth and clean water & dried using a soft cotton cloth.  Bath / shower cleaning 

products, even non-scratch ones could damage the finished surface.

MAINTENANCE

We advise that the valves, check valves and filters be regularly serviced particularly in hard water areas. The check 

valves along with the filters are contained in the retaining nut. The water supplies must be isolated remotely from the 

valve before removal. 

TMV2 approved valves shall be tested against the original set temperature results once a year. When testing is due the 

following performance checks shall be carried out.

1.  Measure the mixed water temperature at the outlet.

2.  Carry out the cold fail-safe shut off test by isolating the cold water supply to the TMV, wait for 5 seconds if water is 

still flowing check that the temperature is below 46 degrees C.

3.  If there is no significant change to the set outlet temperature (+/- 2°C or less change from the original setting) and 

the fail safe shut off is functioning, then the valve is working correctly and no further service work is required.

If further maintenance should be required contact Roper Rhodes for details.  Please see contact details on the back  

page of this document.

Problem

Shower will not run hot enough when first installed

Cold water running back through the valve into the hot water 

system.

Solution

Check for debris

Check hot water temperature

Check and clean the check valve cartridges and filters 

located under the check valves.

Summary of Contents for SV2207

Page 1: ...ched stabilised further action is required It is important to establish that the incoming water supplies still satisfy the initial guidance and also that no additional draw off variation that could affect performance has occurred The material selection for this valve has excellent resistance to scale build up and is designed such that there are no serviceable parts beyond items 1 2 as described pr...

Page 2: ... a position that maintenance of the TMV and its valves and the commissioning and testing of the TMV can be undertaken The fitting of strainers is recommended as close as is practicable to the water supply inlets of the thermostatic mixing valve HIGH PRESSURE LOW PRESSURE Maximum Static Pressure BAR Flow Pressure Hot Cold BAR Hot Supply Temperature C Cold Supply Temperature C 10 0 5 to 5 55 to 65 E...

Page 3: ... deviate by more than 2 C of the initial set recorded result Record these findings 5 Record the measuring equipment used for the measurements The above records must be retained and updated during the service life of the TMV If there is a residual flow during the commissioning or the annual verification cold water supply isolation test then this is acceptable providing the temperature of the water ...

Page 4: ...irmly locks the pipe in position Threaded connector Compression fitting Check valve Flow valve STORM BOTTOM OUTLET BAR VALVE SHOWN STORM BOTTOM OUTLET BAR VALVE SHOWN Increase flow Decrease temperature Increase temperature Decrease flow OPERATING STORM BOTTOM OUTLET BAR VALVE SHOWN Temperature Cartridge Connection nut Filter ...

Reviews: