Accura 2350-TEMP User Guide
Chapter 3 Accura 2350-TEMP Operation/Setup
ⓒ
2020 Rootech Inc. All Rights Reserved
Page 31
DO
Screen
Setup item
Range
Default
Type
DO type settings
- Latch: DO status of the contact point remains.
- Pulse: Pulse Period/Pulse On-time, the
occurrence of pulse
Latch
Polarity
Polarity of the DO for the logic value
1) Latch Type
- Normal mode
0: Open point 1: Closed point
- Reverse mode
0: Closed point 1: Open point
2) Pulse Type
- Normal mode
0: The contact point remains open
1: Pulse occurs when the DO point is closed
- Reverse mode
0: The contact point remains closed
1: Pulse occurs when the DO point is open
Normal
Pulse Period
Pulse cycle time for Pulse Type
0.2
–
9.9 secs
1.0 sec
Pulse On-time
1
Pulse-On time for Pulse Type
0.1
–
9.9 secs
0.5 sec
1. When Pulse-On time is shorter than the pulse cycle time, pulse occurs. When it is same as or longer than the pulse
cycle time, pulse continues to occur.
INTERFACE Setup
Temperature
Screen
Setup item
Range
Default
Trend Interval
Trend interval time for changes in temperatures
1
–
10 min
10 min
Max/Min
Clears the Max/Min values on temperatures with
a command to clear the values
-
LCD Backlight
Screen
Setup item
Range
Default
Timeout
30
–
999 sec
60 sec
Brightness
0
–
100 %
70 %
Contrast
1
–
40 %
18 %