Accura 2350-GAS User Guide
Chapter 2 Accura 2350-GAS Operation/Setup
ⓒ
2014 Rootech Inc. All Rights Reserved
Page 19
Communication
Setup
The following parameters can be set up via Modbus communication. Refer to
「
Accura 2300[S]/2350
Communication User Guide
」
for details on communication settings.
Register
Number
Name
Format
Attribute
Description
1261
Module ID for
general setup
Uint16
PRW
Designates the ID of Accura 2350-GAS module to set up
For the module ID assigned to this register, general setup for
registers 1262 and 1263
–
1302 is performed.
Extended setup for registers 3801 and 3802-4000 is also
performed.
Setup range: 0 - 39 Default: 0
1262
Access for
module setup
Uint16
PRW
Base register for accessing registers 1263 - 1302
By reading this register, the data collected from the module ID
assigned to register 1261 can be fetched to registers 1263
–
1302. After a successful fetch, the Bit[15] is indicated as 1.
By writing 1 to this register, data on registers 1263 - 1302 are
applied to the designated module.
1263
Gas threshold
Uint16
PRW
Sets up the threshold value for detection of gas events
An event occurs when the measured value exceeds the threshold
value.
Unit: PPM
Setup range: 110
–
9990 [PPM]
Default: 2000 [PPM]
1264 -
1268
Reserved
1269
Event enable
Uint16
PRW
Sets up the detection mode of gas events
0: (default) Disable 1: Enable
1270
Hysteresis
Uint16
PRW
Sets up the hysteresis value for event detection
The end level of the event is determined by subtracting the
hysteresis value from the threshold value (threshold
–
hysteresis).
Setup range: 10
–
999 [PPM]
Default: 500 [PPM]