Page 40
Menu Items
Order
Menu Item
Range
Default
1
Demand time
1 ~ 60
15
2
Frequency
50Hz, 60Hz
60
3
Reactive power calculation
Method 1
√
Method 2
4
Group auto-return
†
On
√
Off
5
Display energy
3
kWh received
1
kWh delivered
1
kWh total
2
kWh net
2
√
6
Transmission delay time
0~50
5
7
Demo enable
‡
On
Off
√
8
Product serial number
9
Version
X.XX Hardware version
X.XX Firmware version
†
Measurement group C, D automatically returns to A, B after 30 seconds when
“
group auto-return
”
menu item
is on[default].
‡
When operated in demo mode, SETUP LED blinks.
The displayed measurement data in the demo mode are not actual
measurement data but processed data.
1
kWh/kVARh received is positive for
“
view as load
”
,
kWh/kVARh delivered is positive for
“
view as generator
”
.
2
kWh/kVARh net[kWh/kVARh received
–
kWh/kVARh delivered],
kWh/kVARh total[kWh/kVARh re kWh/kVARh delivered].
3
The
”
Display energy
”
menu item lets users select the energy value [kWh
net, kWh received, kWh delivered, or kWh total] to show first in group c in the display mode.