Chapter 4 Measurements
Accura 3300E User Guide
Page 70
ⓒ
2015 Rootech Inc. All Rights Reserved
Measurements according to Voltage Connection Modes
Voltage, current and power measurements are performed according to voltage connection modes
as follows.
Three Phase 4 Wire Connection
Fig 4.1 Connection with 3 PTs and 3 CTs, Wiring Mode = 3P4U (3P4W Connection)
Voltage Measurement
Vector Diagram
Item
Description
V
1
V
2
V
3
V
N
: Voltage of connected N terminal
Line to neutral
voltage sensing
▶
Sensing line to neutral voltage[V1, V2,
V3] based on the wired VN terminal
voltage (real line to neutral voltage)
V
A
= V1
V
B
= V2
V
C
= V3
Calculation of line
to line voltage
V
AB
= V
A
–
V
B
= V1
–
V2
V
BC
= V
B
–
V
C
= V2
–
V3
V
CA
= V
C
–
V
A
= V3
–
V1
V
N