Accura 2350-TEMPS User Guide
Chapter 2 Accura 2350-TEMPS Operation/Setup
ⓒ
2020 Rootech Inc. All Rights Reserved
Page 21
Communication
Setup
The following parameters can be set up via Modbus communication. Refer to
「
Accura 2300/2350
Communication User Guide
」
for details on communication settings.
Register
Number
Name
Format Attribute Description
1261
Module ID
for general
setup
Uint16
PRW
Designates the ID of Accura 2350-TEMPS module to set up
For the module ID assigned to this register, general setup for
registers 1262 and 1263
–
1302 is performed.
Extended setup for registers 3801 and 3802-4000 is also
performed.
Setup range: 0 - 39 Default: 0
1262
Module setup
access
Uint16
PRW
Base register for accessing registers 1263 - 1302
By reading this register, the data collected from the module ID
assigned to register 1261 can be fetched to registers 1263
–
1302. After a successful fetch, the Bit[15] is indicated as 1.
By writing 1 to this register, data on registers 1263 - 1302 are
applied to the designated module.
1263
Temperature
unit
Uint16
PRW
Sets up the temperature display unit
0 : (default)
℃
, 1 :
℉
1264
Event enable
Uint16
PRW
Sets up event detection mode
Bit[0] : Internal overtemperature event
0 : (default) Disable, 1 : Enable
Bit[2] : External overtemperature event
0 : (default) Disable, 1 : Enable
Bit[4] : Over event on temperature difference
0 : (default) Disable, 1 : Enable
1265
Temperature
threshold
Uint16
PRW
Sets
up
the
threshold
value
for
internal/external
overtemperature events
It is the start level at which the event occurs.
1266
Temperature
hysteresis
Uint16
PRW
Sets
up
the
hysteresis
value
for
internal/external
overtemperature events
End level of the event: threshold
–
hysteresis
1267
Difference
temperature
threshold
Uint16
PRW
Sets up the threshold value for the event on the temperature
difference
It is the start level at which the event occurs.
1268
Difference
temperature
hysteresis
Uint16
PRW
Sets up the hysteresis value for the event on the temperature
difference
End level of the event: threshold
–
hysteresis