Item
Description
Start level
Threshold value for event detection
End level
Threshold value
–
hysteresis value
Start event
A start event occurs when the measured value exceeds the threshold value for event detection
and the definite time elapses. A start event occurs again only if the measured value rises above
the threshold value again after the value drops below the end level and an end event occurs.
The Event LED blinks red only when a start event occurs.
End event
An end event occurs when the measured value drops below the end level. The color of the
Event LED can be changed to green by pressing the SET button.
Hysteresis
When the measured values often exceed and fall below the threshold value for event detection,
it can cause multiple events to occur. Thus, for effective event management, it is necessary to
set up a proper hysteresis level. The default hysteresis value for each event is 1
℃
, and it can be
set up via communication.
Display Mode
Automatic Display
Accura 2350-TEMPS module automatically displays the module ID and the
i
nternal/external temperature
of the panel where it is installed in the following sequence. Short press the SET button in the display
mode to move to the setup mode.
ID
Internal Temperature
External Temperature
ID Display
Display
ID [d][d]
1
Accura 2350 ID
2
1.
d
→
decimal
number
2.
Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura
2350 modules as a factory default value.
Accura 2350 ID
ID
Description
Communication ID
ID 0 - 39
ID of Accura 2350 module that enables communication
Conflict ID
Redundant
IDs
There are more than 2 identical IDs.
Communication unavailable
Standby ID
ID 255
Module ID for checking connection status
Communication unavailable