background image

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for Accura 2350-IDC

Page 1: ......

Page 2: ...have received appropriate training for high voltage and current devices Caution If hazardous voltages are mishandled while installing and operating the product in the field it can cause serious injury...

Page 3: ...ions and the manual before making orders In the absence of written agreements Rootech Inc assumes no liability for applications assistance customer s system design or infringement of patents or copyri...

Page 4: ...a refund for the product for when the warranty period for the product expired or issues related to the product are not applicable for warranty terms and conditions Limitation of Warranty The Warranty...

Page 5: ...asibility It is the original purchaser s responsibility to determine the suitability of the product and associated documentation The original purchaser should acknowledge that 100 up time is not reali...

Page 6: ...nts sections Added environmental conditions including temperature and humidity Deleted content on the external power supply Updated content on events and added the communication setup section 1 21 Apr...

Page 7: ...Power Supply 13 Functions 13 Button Operation 15 LCD Screen 16 Display Mode 16 Setup Mode 17 Communication Setup 20 LED Indicators 22 Chapter 3 Accura 2300 S Operation Setup 23 Display Mode of Accura...

Page 8: ...2 Fig 2 1 Accura 2350 IDC Front 13 Fig 2 2 Analog Input DC Current 14 Fig 2 3 Start Event End Event of Over Event 19 Fig 2 4 Start Event End Event of Under Event 19 Fig 3 1 DC Current Screen of Channe...

Page 9: ...Inc All Rights Reserved Page 9 Chapter 1 Installation and Wiring Before Installation Components Fig 1 1 Accura 2350 IDC Components Accura 2350 IDC Mounting wings L S Two screws RJ12 6C communication l...

Page 10: ...Chapter 1 Installation and Wiring Accura 2350 IDC User Guide Page 10 2014 Rootech Inc All Rights Reserved Fig 1 4 Accura 2350 IDC Side...

Page 11: ...ra 2350 IDC User Guide Chapter 1 Installation and Wiring 2014 Rootech Inc All Rights Reserved Page 11 Installation Panel Mounting Fig 1 5 Panel Mounting DIN Rail Mounting Fig 1 6 DIN Rail Mounting Wir...

Page 12: ...ect the cable to the DC current input ports according to the positive negative polarity of the ports Connect the RJ12 6C communication line to the RJ12A RJ12B port Accura 2350 IDC module receives powe...

Page 13: ...cription Power supply Receives power from Accura 2300 S through the RJ12 6C communication line Current consumption 0 11A 5V RJ12 power supply Functions Analog Input 8 DC Current Channels Ch 1 Ch 2 Ch...

Page 14: ...between channels Input resistance Higher than 2 M Accuracy 0 5 FS 1 Event Over Under 2 event selectable based on the threshold value for each channel 1 Full Scale FS indicates 20 mA 2 An Over event in...

Page 15: ...etup Mode Short press 1 Move to the setup mode The setup menu is sequentially selected each time the SET button is pressed Long press 2 Preset values blink and can be changed Short press Select a pres...

Page 16: ...es of the LCD screen ID Display Display ID d d 1 Accura 2350 ID 2 1 d decimal number 2 Module IDs are divided into as follows The standby ID 255 is assigned to all Accura 2350 modules as a factory def...

Page 17: ...for Channel 8 Hysteresis for Channel 8 Note If there is no button operation for 10 seconds in the setup mode the screen automatically returns to the display mode ID Setup ID Description ID d d 1 Defau...

Page 18: ...Over event An end event occurs when the measured value drops below the end level Hysteresis When the measured values often exceed and fall below the threshold value for event detection it can cause mu...

Page 19: ...20 0 mA 1 d decimal number Hysteresis Setup for Each Channel 1 8 Channel hy Hysteresis Setup Range d d d 1 Default 0 4 mA Hysteresis value Setup range 0 1 FS 0 5 20 0 mA 1 d decimal number Fig 2 3 St...

Page 20: ...p the method of displaying the measured current value ranging from 20 to 20mA If it is set to 1 the negative sign of current is removed and only the positive current value is displayed 0 20 to 20 mA p...

Page 21: ...Float32 PRW Sets up the minimum measured value of channel 1 Expressed as a percentage value of the full scale value The value less than the minimum measured value is processed as zero The Full Scale...

Page 22: ...rrent measurement data are displayed the LED of the corresponding channel lights up LED Indicators IDC1 and IDC2 LEDs turned on Displays the DC input current of channels 1 and 2 IDC3 and IDC4 LEDs tur...

Page 23: ...Supports setup for various parameters of Accura 2300 S 2350 network connection PT communication event etc Event log mode Displays event logs such as Dip and Swell events Note The SETUP LED remains On...

Page 24: ...the EVENT LED blinks and the color of the LCD backlight changes from WHITE to RED to notify users of the occurrence of the event Users can enter the event log mode by long pressing the EVENT button o...

Page 25: ...Log Mode of Accura 2300 S Details of the events that occurred in the IDC module can be checked on the Event Log screen of Accura 2300 S Each event consists of start and end events Fig 3 6 Start Event...

Page 26: ...l Rights Reserved Users can check the event occurrence time year month date hour minute second and millisecond for each event by pressing the Down button on Accura 2300 S s Event Log screen Fig 3 8 Ev...

Page 27: ...requency V FREQ Current I Power Power Factor P PF Demand DEMAND d d d d d d d d d d d d d d tEMP Temp 3 Temperature Date and Time tot Total dEL Deliverd rEC Received nEt NET 2 Type of Active Energy MO...

Page 28: ...nt Over Under 2 event selectable based on the threshold value for each channel 1 Full Scale FS indicates 20 mA 2 An Over event indicates an event where the measured value rises above the threshold An...

Page 29: ...Accura 2350 IDC User Guide Appendix B Ordering Information 2014 Rootech Inc All Rights Reserved Page 29 Appendix B Ordering Information Module Name Accura 2350 IDC...

Page 30: ...300 2350 Accura 2300S 2350 Accura 2700 2750 Accura 3000 Accura 3300E Accura 3300S 3300 Accura 3500S 3500 Accura 3550S 3550 Accura 3700 Accura 5500 and Accura 7500 are trademarks of Rootech Inc Contact...

Reviews: