Step 9 • 

Bolt tightening 

should be done evenly, alter-

nating to diametrically op-

posite positions at approxi-

mately 20 ft-lbs. increments 

to bring bolts to recom-

mended tightness.

Style FCA501

(continued from front)

Step 6B • 

Flanged Couplings without Anchor Pins:

 

Slide the flanged coupling assembly onto the pipe. Position 

the the pipe and flanged coupling against the mating flange.  

Assemble the flange joint using flange bolts.

NOTE:

50 ft-lbs. torque = 12" wrench w/50 lbs. force

70 ft-lbs. torque = 12" wrench w/70 lbs. force

95 ft-lbs. torque = 12" wrench w/95 lbs. force

After pipe is pressurized check for leakage 

and tighten as necessary.

7

Step 8 • 

Slide end ring into 

position (engaging the through 

bolts) against the gasket.

8

Step 7 • 

The pipe should be 

centered such that the space 

between the OD of the pipe 

and the ID of the FCA body is 

even all around the pipe.  Slide 

flanged coupling gasket into 

position with the beveled edge 

engaging the beveled end of the flanged coupling body.

PRECAUTIONS

1.   Check diameter of pipe to make sure you are using the correct size coupling; also check gasket to make 

sure it is the size you think it is.

2.  Clean pipe to remove dirt and corrosion from pipe surface. Lubrication and additional cleaning should be 

provided by brushing both the gasket and plain pipe end with soapy water or approved pipe lubricant per 

ANSI/AWWA C111/A21.11.

3.  Make sure no foreign materials lodge between gasket and pipe.
4.  Avoid loose fitting wrenches, or wrenches too short to achieve proper torque.
5.  Keep threads free of foreign material to allow proper tightening.
6.  Take extra care to follow proper bolt tightening procedures and torque recommendations. Bolts are often not 

tightened enough when a torque wrench is not used. 

7.  Pressure test for leaks before backfilling.
8.  Backfill and compact carefully around pipe and fittings.
9.  When reinstalling parts with stainless steel hardware, there may be a loss in pressure holding ability due to 

worn or damaged threads during the original installation. 

 

COMMON INSTALLATION PROBLEMS

1.  Bolts  are not tightened to the proper torque.
2.  Rocks or debris between pipe and gasket.
3.   Dirt on threads of bolts or nuts.
4.  Not enough pipe insertion when installing anchor pins.

FCA501 SIZE END RING BOLTS

FLANGE BOLTS

3"

60 - 70 FT-LBS

75 - 85 FT-LBS

4"

60 - 70 FT-LBS

75 - 85 FT-LBS

6"

75 - 85 FT-LBS

90 - 100 FT-LBS

8"

75 - 85 FT-LBS

90 - 100 FT-LBS

10"

60 - 70 FT-LBS

150 - 160 FT-LBS

12"

85 - 95 FT-LBS

150 - 160 FT-LBS

16"

60 - 70 FT-LBS

235 - 245 FT-LBS

RECOMMENDED TORQUE