E-135
Specifications E-134
/
Dimensions E-135
/
Connection E-135
ON/OFF Control of a Single Fan
●
When the temperature within the enclosure rises to a specified level
(preset temperature), the thermostat activates the fan automatically.
Once the enclosure interior is sufficiently cooled, it causes the fan to
stop. This is a great way to save energy and reduce noise.
Application Example
◇
AM1-XA1
AM1-WA1
Connection Example
◇
Cooling Module
FM
Series
AC Power Supply
AM1-WA1
AM1-XA1
ON/OFF Control of Multiple Fans
●
Multiple fans can be effectively controlled in cases where more than
one fan is needed to produce the required air flow or static pressure.
For example, a thermostat can control a maximum of nine
MU1238
type fans. (A six-fan configuration is shown.)
Application Example
◇
MU1238
AM1-WA1
AM1-XA1
Connection Example
◇
AC Power Supply
AM1-WA1
AM1-XA1
When using 6 fans (
●
MU1238
)
Thermostat
Number of
Fans
Input
W
Noise Level
dB (A)
ON
6
84
51
OFF
–
0
0
Applicable Products
■
Input
Series
Model
Number of Connectable Fans
Single-Phase
AC-Input
MU
Series
All models
9
FM
Series
All models
9
MRS
Series
MRS25
1
MRS20
2
MRS18
2
MRS16
5
MB
Series
MB1665
✽
MB1255
1
MB1040
4
MB840
7
MB630
,
MB520
9
MF
Series
MF930
,
MF915
5
For
✽
MB1665
type, thermostats can be used only for single-phase 100 VAC and 200 VAC
products.
Note:
Impression of voltage exceeding the rated voltage may shorten the service life of the product.
●
Dimensions
■
Unit = mm (in.)
Mass: 45 g (1.6 oz.)
AM1-WA1
:
E108
AM1-XA1
:
E108
1
2
60
(
2.36
)
33
(
1.30
)
35
(
1.38
)
Effective Use of the Thermostat
■
Using a fan with a thermostat provides automatic on/off control of the fan and air flow switching.