MCX2D / MCX4D Installation Manual 

Firmware version: 1.1.18 and newer 

Hardware version: 1.0 

Document version: Rev. B 

 

 

This  document  contains  minimum  information  that  is  necessary  for  initial  setup 
and  installation  of  the  device.  The  detailed  description  of  configuration 
parameters  and  functionalities  is  specified  in  respective  Operating  Manual 
available a

www.roger.pl

I

NTRODUCTION

 

The  expander  is  designed  to  operate  in  RACS  5  system  as  peripheral  device 
connected  to  RS485  bus  of  MC16  access controller.  MCX2D expander  enables 
to control up to two doors by MC16 controller while MCX4D expander enables to 
control  up  to  four  doors  by  MC16  controller.  MCX2D  expander  is  installed  in 
MC16-PAC-2-KIT  while  MCX4D  expander  is  installed  in  MC16-PAC-3-KIT  and 
MC16-PAC-4-KIT. 
Factory new device is configured with default settings including ID=100 address. 
Programming  of 

expander’s  configuration  parameters  is  optional  and  is  not 

necessary in most cases. Configuration of the expander with RogerVDM requires 
RUD-1 interface. 

C

ONFIGURATION WITH 

R

OGER

VDM

 

P

ROGRAM

 

 

Fig. 1 Connection of the expander to RUD-1 interface for configuration 

Programming procedure with RogerVDM software: 

1.  Connect  the  device  to  RUD-1  interface  (fig.  1)  and  connect  the  RUD-1  to 

computer’s USB port. 

2.  Place jumper on MEM contacts (fig. 3). 
3.  Restart  the  device  by  pressing  RST  button  and  RUN  LED  indicator  will 

pulsate. 

4.  Start  RogerVDM  program,  select 

MCX  v1.x

  device, 

v1.x

  firmware  version, 

RS485

 communication channel and serial port with RUD-1 interface. 

5.  Click 

Connect,

  the  program  will  establish  connection  and  will  automatically 

display 

Configuration

 tab. 

6.  Enter  unoccupied  RS485  address  in  range  of  100-115  (if  necessary)  and 

other settings according to requirements of specific installation. 

7.  Click 

Send to Device

 to update the configuration. 

8.  Optionally  make  a  backup  by  clicking 

Send  to  File… 

and  saving  settings  to 

file on disk. 

9.  Remove  jumper  from  MEM  contacts  and  disconnect  device  from  RUD-1 

interface. 

M

EMORY RESET PROCEDURE AND MANUAL ADDRESSING

 

Memory reset procedure resets all settings to factory default ones and it enables 
to manually configure the address on RS485 bus. 

1.  Remove all connections from LCK1 and DC1 lines. 
2.  Place jumper on MEM contacts (fig. 3). 
3.  Connect LCK1 and DC1 lines. 
4.  Restart  the  device  by  pressing  RST  button  and  ACL  LED  indicator  will 

pulsate. 

5.  Disconnect  LCK1  and  DC1  lines  and  RUN  LED  indicator  will  pulsate.  The 

number  of  consecutive  flashes  will  correspond  to  expander’s  address  on 
RS485 bus. 

6.  Press  RST button in a  certain moment to select certain  address  (table 1) or 

press  RST  button  after  16  flashes  when  ACL  and  RUN  LED  indicators  are 
switched on to select default ID=100 address. 

7.  Remove jumper from MEM contacts and restart the device. 

 
 
 

Table 1. RS485 address encoding 

Number  of  RUN 
LED flashes 

RS485 address 

Number  of  RUN 
LED flashes 

RS485 address 

101 

109 

102 

10 

110 

103 

11 

111 

104 

12 

112 

105 

13 

113 

106 

14 

114 

107 

15 

115 

108 

16 

100 

 
Example: 
In  order  to  select  ID=105  address  within  memory  reset  procedure,  press  RST 
button after 5 flashes of RUN LED indicator. 

B

ACKUP BATTERY CHARGING

 

According  to  fig.  4  the  expander  charges  backup  battery.  Table  2  includes 
current values which ensure 80% battery charging within 24 hours (according to 
EN-60839  standard).  The  charging  current  is  selected  by  means  of  jumpers  on 
expander board (fig. 3). 

Table 2. Backup battery charging 

Charging current 

Contacts 

Battery capacity 

300mA 

300 

7Ah 

600mA 

600 

17Ah 

900mA 

900 

24Ah 

F

IRMWARE UPDATE

 

The  update  requires  connection  of  expander  to  computer  with  RUD-1  interface     
(fig.  2)  and  starting  RogerVDM  software.  The  latest  firmware  file  is  available  at 

www.roger.pl

Firmware update procedure: 

1.  Connect  the  device  to  RUD-1  interface  (fig.  2)  and  connect  the  RUD-1  to 

computer’s USB port. 

2.  Place jumper on FDM contacts (fig. 3). 
3.  Restart the device by pressing RST button and TXD LED indicator will switch 

on. 

4.  Start RogerVDM program and in the top menu select 

Tools

 and then 

Update 

firmware

5.  In  the  opened  window  select  device  type,  serial  port  with  RUD-1  interface 

and path to firmware file (*.hex). 

6.  Click 

Update 

to start firmware upload with progress bar in the bottom. 

7.  When the update is finished, remove FDM jumper and restart the device. 

 

Fig. 2 Connection of the expander to RUD-1 interface for firmware update 