Roger Access Control System 

MCI-2 Installation Manual 

 

 

Firmware version: 1.0.30.265 and newer 

Document version: Rev. A 

 

 

I

NTRODUCTION

 

MCI-2  interface  is  a  converter  between  RS485  (EPSO3)  protocol  and  RACS 
CLK/DTA  protocol.  The  interface  is  used  to  connect  MCT  series  terminal  of 
RACS  5  system  to  PR  series  controller  of  RACS  4  system  or  HRC  series 
controller  of  hotel  automation  system.  Factory  new  device  does  not  require  low 
level  configuration  and  can  be  operated  with  default  settings  (RACS  CLK/DTA 
address  ID0).  Low  level  configuration  of  the  MCI-2  interface  with  RogerVDM 
requires RUD-1 interface. 

C

ONFIGURATION WITH 

R

OGER

VDM

 

P

ROGRAM

 

 

Fig. 1 Connection of the MCI-2 to RUD-1 interface for configuration 

Programming procedure with RogerVDM software: 

1.  Connect  the  device  to  RUD-1  interface  (fig.  1)  and  connect  the  RUD-1  to 

computer’s USB port. 

2.  Remove jumper from MEM contacts (fig. 3) and restart the device (short RST 

contacts for a moment or switch power supply off and on). 

3.  Within  5  seconds  when  orange  LED  SYSTEM  indicator  pulsates  twice  per 

second,  place  jumper  on  MEM  contacts  and  LED  SYSTEM  indicator  will 
pulsate quickly. 

4.  Start  RogerVDM  program,  select 

MCI-2  v1.x

  device, 

v1.0

  firmware  version, 

RS485

 communication channel and serial port with RUD-1 interface. 

5.  Click 

Connect,

  the  program  will  establish  connection  and  will  automatically 

display 

Configuration

 tab. 

6.  If  necessary,  define  address  on  RACS  CLK/DTA  bus  and  other  settings 

according to requirements of specific installation. 

7.  Click 

Send to Device

 to update the configuration. 

8.  Optionally  make  a  backup  by  clicking 

Send  to  File… 

and  saving  settings  to 

file on disk. 

9.  Leave jumper on MEM contacts and disconnect device from RUD-1 interface. 

F

IRMWARE UPDATE

 

The  update  requires  connection  of  MCI-2  to  computer  with  RUD-1  interface     
(fig.  2)  and  starting  RogerVDM  software.  The  latest  firmware  file  is  available  at 

www.roger.pl

Note:  After  firmware  update  it  may  be  necessary  to  restore  factory  default 
settings. Current configuration of device can be exported to file using RogerVDM 
program before firmware update. 

Firmware update procedure: 

1.  Connect  the  device  to  RUD-1  interface  (fig.  2)  and  connect  the  RUD-1  to 

computer’s USB port. 

2.  Place jumper on FDM contacts (fig. 3). 
3.  Restart the device (short RST contacts for a moment or switch power supply 

off and on). 

4.  Start RogerVDM program and in the top menu select 

Tools

 and then 

Update 

firmware

5.  In  the  opened  window  select  device  type,  serial  port  with  RUD-1  interface 

and path to firmware file (*.hex). 

6.  Click 

Update 

to start firmware upload with progress bar in the bottom. 

7.  When the update is finished, remove FDM jumper and restart the device. 
8.  If  orange  LED  SYSTEM  indicator  slowly  pulsates  after  restart  then  place 

jumper on MEM contacts, wait 5 seconds and restart device to restore factory 
default settings. 

 

Fig. 2 Connection of the MCI-2 to RUD-1 interface for firmware update 

A

PPENDIX

 

 

Fig. 3 MCI-2 interface 

Table 1. MCI-2 screw terminals 

Screw terminal 

Description 

+12V 

12VDC power supply 

GND 

Ground 

RS485 bus, line A 

RS485 bus, line B 

CLK 

RACS CLK/DTA bus, line CLOCK 

DTA 

RACS CLK/DTA bus, line DATA 

 

Table 2. MCI-2 indicators 

Name 

Colour 

Description 

LED 
SYSTEM 

Orange 

Pulsing: Configuration error 
Quick pulsing: Device in configuration mode 

LED 
OPEN 

Green 

LED 
STATUS 

Red 

Pulsing: Communication lost on RS485 (EPSO3) bus 

Green 

Pulsing: Communication lost on RACS CLK/DTA bus 

 

Table 3. Specification 

Supply voltage 

Nominal 12VDC, min./max. range 10-15VDC 

Current 

consumption 

(average) 

25mA 

Distances 

Up  to  1200  m  between  interface  and  MCT  reader 
(RS485) 
Up  to  150m  between  interface  and  PR  or  HRC 
controller (RACS CLK/DTA) 

IP Code 

IP20 

Environmental 

class 

(according 

to 

EN 

50133-1) 

Class  I,  indoor  general  conditions,  temperature:  +5°C 
to  +40°C,  relative  humidity:  10  to  95%  (no 
condensation) 

Dimensions W x S x G   36 x 55 x 47 mm 
Weight 

~16g 

Certificates 

CE 

 
 
 

Reviews: