Cerber
®
C41V1/Cerber
®
C41V4
H
OOKUP
I
NSTALLATION
& P
ROGRAMMING
B
OOK
18
[ 0 ]
E
NTRY
/E
XIT
Z
ONE
(
D
ELAYED
ZONE
)
An
Entry/Exit
zone is usually used for Entry/Exit doors. The Exit Delay starts
when the system is armed. The zone may be opened and closed during the
delay without causing an alarm.
When the Exit Delay expires, zone opening will start the Entry Delay. During
the Entry Delay, the keypad buzzer will sound continuously to indicate that
the system should be disarmed. If the system is disarmed before the Entry
Delay expired, no alarm will be generated.
Entry and Exit Delay times may be independently programmed for 1 to 255
seconds in section 11. The default settings are 120 seconds for the Exit
Delay and 30 seconds for the Entry Delay.
This zone type can be programmed for Forced arming.
[ 1 ]
I
NSTANT
Z
ONE
Instant
zones are normally used for door and window contacts.
Instant
zones
are disabled during Exit Delay, but will generate an instant alarm if opened
after Exit Delay expired.
The Exit Delay is the same as for Delayed zones and is 120 seconds by
default.
[ 2 ]
F
OLLOWER
Z
ONE
The
Follower
zones are used with interior motion detectors and follow the
standard Exit Delay. If entering the system is done through a
Delayed
zone,
then the
Follower
zone will have the standard Entry Delay. If entering the
system is done through a
Follower
zone without coming through a
Delayed
zone, an alarm will be generated.
This zone type can be programmed for Forced arming.
[ 4 ]
24-H
OUR
Z
ONE
The 24-hour zones are permanently active. If such a zone is tripped, an alarm
will be generated even if the system is disarmed.
The second digit of each group represents the alarm type. There are
six alarm types:
[ 0 ] S
TEADY
Send an alarm message and the siren will be enabled.
[ 1 ] P
ULSE
Send an alarm message and the siren will be enabled in pulse.
After an pulsing alarm occurring all the other audible alarms will be pulsing
alarms, until the siren will be stopped.