Flw2 Config
Configuration
of Flow
Sensor 2
0 or 1
0
0
This setting configures the use of the
second flow sensor. Enter [0] to use the
sensor on reject or [1] to use the sensor
on permeate.
54
Flw1 K Fact
K Factor for
Flow Sensor 1
0-10,000
0000.0
100
K factor (in pulses per gallon) for the first
flow sensor.
55
Flw2 K Fact
K Factor for
Flow Sensor 2
0-10,000
0000.0
100
K factor (in pulses per gallon) for the
second flow sensor.
56
Flw3 K Fact
K Factor for
Flow Sensor 3
0-10,000
0000.0
100
K factor (in pulses per gallon) for the
third flow sensor.
57
High Recovery SP
High Flow
Recovery
Setpoint
0-100
00
90
Recovery setpoint (in percent) which
activates the high pressure alarm.
58
High Recovery DB
High Flow
Recovery
Deadband
0-100
0.0
10
Deadband (in percent) through which the
recovery value must pass before the
high recovery alarm is released.
59
High Recovery TD
High Flow
Recovery
Time Delay
0-255
000
20
Delay (in percent) before the high
recovery alarm is activated once the
current value rises above the setpoint.
60
High Recovery
Shtdwn
High Flow
Recovery
Shut Down
Delay
0-255
000
10
Delay (in seconds) before the system
shuts down after the high recovery alarm
is activated.
61
Low Recovery SP
Low Flow
Recovery
Setpoint
0-100
00
90
Recovery setpoint (in percent) which
activates the low pressure alarm.
62
Low Recovery DB
Low Flow
Recovery
Deadband
0-100
0.0
10
Deadband (in percent) through which the
recovery value must pass before the low
recovery alarm is released.
63
Low Recovery TD
Low Flow
Recovery
Time Delay
0-255
000
20
Delay (in seconds) before the low
recovery alarm is activated once the
current value drops below the setpoint.
64
Low Recovery
Shtdwn
Low Flow
Recovery
Shut Down
Delay
0-255
000
10
Delay (in seconds) before the system
shuts down after the low recovery alarm
is activated.
†
System must be shut down to change these settings.