Programming and Parameters
3-41
UT
IL
IT
Y (F
ile E)
D
iag
no
st
ic
s
215
[Last Stop Source]
Displays the source that initiated the most
recent stop sequence. It will be cleared
(set to 0) during the next start sequence.
Default:
Options:
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Read Only
“Pwr Removed”
“DPI Port 1”
“DPI Port 2”
“DPI Port 3”
“Reserved”
“DPI Port 5”
“Reserved”
“Digital In”
“Fault”
“Not Enabled”
“Sleep”
“Jog”
“Autotune”
“Precharge”
“Safe Off”
216
[Dig In Status]
Status of the digital inputs.
Read Only
thru
217
[Dig Out Status]
Status of the digital outputs.
Read Only
thru
218
[Drive Temp]
Present operating temperature of the
drive power section.
Default:
Min/Max:
Units:
Read Only
–/+100 degC
0.0/100.0%
1.0 degC
0.1%
Fi
le E
Gr
oup
No.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Relate
d
E C
E C
E C v3
0
0
0
0
0
0
x
x
0
0
0
0
0
0
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=Input Present
0
=Input Not Present
x =Reserved
Bit #
Digital In1
Digital In2
Digital In3
Digital In4
Digital In5
Digital In6
In1 DLogRslt
(1)
In2 DLogRslt
(1)
In3 DLogRslt
(1)
In4 DLogRslt
(1)
In5 DLogRslt
(1)
In6 DLogRslt
(1)
Nibble 1
Nibble 2
Nibble 3
Nibble 4
(1)
Enhanced firmware 2.001 & later.
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=Output Energized
0
=Output De-energized
x =Reserved
Bit #
Digital Out1
Digital Out2
Nibble 1
Nibble 2
Nibble 3
Nibble 4
E C
E C
Summary of Contents for PowerFlex 70