Rockwell Automation Publication 1783-UM007F-EN-P - September 2016
525
Cables and Connectors
Appendix D
You can use Category 3, 4, or 5 cabling when connecting to 10BASE-T-
compatible devices. You must use Category 5 cabling when connecting to
100BASE-TX-compatible devices.
and
show the cable schematics.
Figure 72 - Two Twisted-pair Crossover Cable Schematics
Figure 73 - Four Twisted-pair Crossover Cable Schematics
Dual-purpose Ports (combo ports)
The Ethernet port on a dual-purpose port uses standard RJ45 connectors. The
following figure shows the pinouts.
Figure 74 - Ethernet Port RJ45 Connector
The SFP module slot on a dual-purpose port uses SFP modules for fiber-optic
ports. The auto-MDIX feature is enabled by default.
IMPORTANT
Use a four twisted-pair, Category 5 cable when connecting to a 1000BASE-T-
compatible device or PoE port.
Switch
3 TD+
6 TD–
1 RD+
2 RD–
Switch
3 TD+
6 TD–
1 RD+
2 RD–
H5579
1 TPO+
2 TPO-
3 TP1+
6 TP1-
1 TP0+
Switch
Switch
2 TP0-
3 TP1+
6 TP1-
4 TP2+
5 TP2-
7 TP3+
8 TP3-
4 TP2+
5 TP2-
7 TP3+
8 TP3-
2 3
1
4 5 6 7 8
Pin
Label
1
2
3
4
5
6
7
8
TP0+
TP0-
TP1+
TP2+
TP2-
TP1-
TP3+
TP3-
Summary of Contents for ArmorStratix 5700 series
Page 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Page 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Page 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Page 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Page 547: ......