Rockwell Automation Publication 1783-UM007F-EN-P - September 2016
379
Monitor the Switch
Chapter 8
Table 98 - Stratix 5400 Port Status Indicators
Mode
Status
Description
Status
In Status mode, the port status indicators show the connection and activity status of the port. Status mode is the default mode. You can choose Status mode via
the View pull-down menu in Device Manager. You can also choose Status mode by pressing the Disp. Mode button on the physical switch until all mode status
indicators on the switch turn off.
Off
No link present on the port.
Solid green
Port link; no activity.
Flashing green and off
Link is active and healthy.
Alternating green and
amber
There is a fault or error on the link.
Solid amber
The port is disabled.
Duplex
In Duplex mode, the port status indicators show the Duplex mode (Full-duplex or Half-duplex) of the ports. The 10/100/1000 ports operate only in Full-duplex
mode.
Off
The port is not operating.
Solid amber
The port is operating in Half-duplex mode.
Solid green
The port is operating in Full duplex mode.
Speed
In Speed mode, the port status indicators show the operating speed of the ports.
Off
The port is not operating.
Solid amber
The port is operating at 10 Mbps.
Solid green
The port is operating at 100 Mbps.
Flashing green
The port is operating at 1000 Mbps.
PRP
In PRP mode, the port status indicators show the status of Parallel Redundancy Protocol (PRP). To configure PRP, see
.
Off
PRP is disabled or not in use on the port.
Solid green
PRP is active on the port.
DLR—Not functional as of the current release.
Power/PoE
In Power or PoE mode, the port status indicators show the status of PoE on switch models with PoE capability.
The Power mode available via the View pull-down menu in Device Manager is the same as the PoE mode available via the Disp. Mode button on the physical
switch.
Off
PoE is disabled on the port.
Solid green
PoE is enabled on the port. The switch port is providing power.
Flashing green and amber
PoE is denied because it exceeds the power capacity of the switch.
Flashing amber
PoE is denied because it exceeds the configured power limit for the switch port.
Summary of Contents for ArmorStratix 5700 series
Page 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Page 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Page 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Page 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Page 547: ......