144
Rockwell Automation Publication 1783-UM007F-EN-P - September 2016
Chapter 5
Install Stratix 5700 Switches
Wire the Power over Ethernet
DC Power Source
This procedure applies only to switches with PoE ports.
The switch must be wired and grounded.
Power input requirements depend on your application.
1. Measure a length of 0.82…0.52 mm
2
(18…20 AWG) copper wire long
enough to connect to the DC power source.
2. Using an 18-gauge wire-stripping tool, strip each of the two wires to
6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.).
Do not strip more than 6.8 mm (0.27 in.) of insulation from the wire.
Stripping more than the recommended amount of wire can leave wire
exposed after installation.
3. Locate the power connector.
WARNING:
The console port is intended only for temporary local programming purposes and not intended for permanent
connection. If you connect or disconnect the console cable with power applied to this module or the programming device on the
other end of the cable, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
ATTENTION:
To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a source compliant with
the safety extra low voltage (SELV) or protected extra low voltage (PELV).
To comply with UL restrictions, this equipment must be powered from a source compliant with Class 2 or Limited Voltage/Current.
Application
Power Supply per Port
Power Consumption
Allen-Bradley Products
PoE only
IEEE 802.3af
44…57V DC (48V DC nom)
15.4 W, max
Switched mode power supplies:
• 1606-XL Standard
• 1606-XLE Essential
• 1606-XLP Compact
• 1606-XLS Performance
PoE and PoE +
IEEE 802.3at Type 2
50…57V DC (54V DC nom)
15.4 W, max for PoE
30 W, max for PoE+
WARNING:
Before performing any of the following procedures, make sure that power is removed from the DC circuit or the area
is nonhazardous before proceeding.
6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.)
31789-M
Summary of Contents for ArmorStratix 5700 series
Page 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Page 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Page 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Page 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Page 547: ......