STEP 3 - Change the heater elements in the overload
block, Fig. 8, for the proper voltage/ampere rating
shown on the motor nameplate.
For every LVC motor starter, a heater coil chart is
located on the inside cover of the motor starter enclo-
sure. See Fig. 14.
Note from the motor nameplate, the full load current
for the new line voltage. Select the heater or heaters
one code number lower than specified in the table of
the heater coil chart which will give a maximum trip
r a t i n g o f a p p r o x i m a t e l y 1 1 5 % o f t h e m o t o r n a m e -
plate current.
S I N G L E P H A S E
For example, on three phase starters, assume it is nec-
essary to pick a heater for a motor with a nameplate
rating of 10.6 amperes.
Reference to the heater coal
chart in Fig. 14, shows that a 10.6 full load motor
ampere rating corresponds to a heater code number,
E-56. Thus, heater number E-55, should be specified
w h i c h w i l l g i v e a m a x i m u m t r i p r a t i n g o f a p p r o x i -
m a t e l y 1 . 1 5 x 1 0 . 6 = 1 2 . 2 a m p e r e s .
of
M o .
C o d e
Mu. No.
T H R E E P H A S E
Summary of Contents for 70-602
Page 2: ...WARNING For your own safety DON T wear gloves when operating a drill press...
Page 19: ...Fig 11 13...
Page 24: ...18 Fig 19 24 Volt Three Phase Magnetic Starter Motor control System...
Page 25: ...Fig 20 24 Volt Three Phase Magnetic Starter Motor Control System 19...
Page 26: ...2 0 Fig 21 24 Volt Three Phase Magnetic Starter Motor Control System...
Page 27: ...Fig 22 24 21 Fig 22 24...
Page 29: ...This page intentionally left blank 2 3...
Page 30: ...2 4 Fig 24 Series 2000 Drilling Machines Direct Drive...
Page 32: ...Fig 25 Fig 25 2 6...
Page 34: ...Fig 26 28 Fig 26...
Page 36: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......