Topic

Page

Important User Information

2

Environment and Enclosure

3

Preventing Electrostatic Discharge

4

Before You Begin

5

Module Identification and Dimensions

5

Observing Precautions for Correct Use

7

Observing Precautions for Safe Use

7

Install the Module

10

Set MAC ID

10

Wiring the Module

10

Working with I/O Connectors

11

Terminal Positions

12

Interpret the Status Indicators

14

Specifications

18

Additional Resources

23

Summary of Contents for 1732DS-IB8

Page 1: ...Enclosure 3 Preventing Electrostatic Discharge 4 Before You Begin 5 Module Identification and Dimensions 5 Observing Precautions for Correct Use 7 Observing Precautions for Safe Use 7 Install the Modu...

Page 2: ...lar installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with resp...

Page 3: ...diated disturbances This equipment is supplied as enclosed equipment It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the S...

Page 4: ...c safe packaging when not in use ATTENTION Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements Personnel...

Page 5: ...d observe all prohibitions of use applicable to this product Never use the products for an application involving serious risk to life or property without first verifying that the system as a whole has...

Page 6: ...s Publication 1732DS IN001D EN P September 2009 1732DS IB8XOBV4 Module Dimensions 1732DS IB8 Module Dimensions 31626 179 mm 7 05 in 70 mm 2 76 in 168 6 mm 6 64 in 68 7 mm 2 71 in 179 mm 7 05 in 70 mm...

Page 7: ...the module before commissioning the system in which the module is incorporated noting that incorrect wiring can lead to loss of safety function Do not apply DC voltages exceeding rated voltages to th...

Page 8: ...esponsible for compliance with applicable standards for the entire system Disconnect the module from the power supply when wiring ATTENTION Safety state of the module and its data is defined as off st...

Page 9: ...capable of switching microloads of 24V DC 5 mA Bulletin 440K 440G or 440H for interlock switch Bulletin 440P or 802T for limit switch Safety sensor Use approved devices complying with the relevant pr...

Page 10: ...hen wiring the module Do not share communication input or output lines with high voltage referring to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Wire correctly after co...

Page 11: ...M12 female I O connectors Input and Output Configuration Input Configuration Pin Signal 1 Test Output n 1 2 Safe Input n 1 3 Input Common 4 Safe Input n 5 Test Output n Output Configuration 1732DS IB8...

Page 12: ...Output male connector DeviceNet and Power Configuration Terminal Positions See the figure and table that show terminal positions DeviceNet Male and Female Configuration Pin Signal 1 Drain 2 V 3 V 4 C...

Page 13: ...24V DC A 5 Test Output 0 E 5 L 24V DC Common 3 B 1 Test Output 3 F 1 S 24V DC 1 B 2 Safety Input 3 F 2 Safety Output 3 2 Switch 24V DC Common B 3 Input Common F 3 L 24V DC Common 3 B 4 Safety Input 2...

Page 14: ...nfiguration wiring and voltages and apply the changes 24V DC Output Power Indicator 1732DS IB8XOBV4 module only State Status Description Recommended Action Off No power No power is applied Apply power...

Page 15: ...green Device in self test The module is performing its power cycle diagnostic tests 1 For recommended action refer to the user manual that covers these modules Network Status Indicator 1 State Status...

Page 16: ...col message 1 For recommended action refer to the user manual that covers these modules Safety Input Status Indicator State Status Description Recommended Action Off Safety input off or module being c...

Page 17: ...ace module Both tags in a dual channel circuit do not have the same value Make sure logic is driving tag values to the same state off or on Flashing red Partner fault detected A fault in the partner o...

Page 18: ...3 Pulse Test Output Output type Current sourcing Pulse test output current 0 7 A Residual voltage max 1 2V Output leakage current max 0 1 mA Short circuit protection Yes Current max 25 mA Current max...

Page 19: ...esence of a single P stuck high or M stuck low short General Specifications 1732DS IB8XOBV4 1732DS IB8 Attribute 1732DS IB8XOBV4 1732DS IB8 Enclosure type rating Meets IP64 65 66 67 69K when product i...

Page 20: ...lb Dimensions HxWxD approx 69 x 179 x 70 mm 2 7 x 7 0 x 2 8 in 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines p...

Page 21: ...Unpackaged Nonoperating Dry Heat 45 85 C 49 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 5 g 10 500 Hz Shock operat...

Page 22: ...ine earth CM on signal ports 2 kV line earth CM on communication ports Reaction Time Input reaction time max 16 2 ms set values of ON OFF delays Output reaction time max 6 2 ms 20 ms relay response ti...

Page 23: ...n when product is marked 1 1732DS IB8XOBV4 1732DS IB8 c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E65584 CE European Union 2004 108 EC EMC Directive complian...

Page 24: ...eturn Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be re...