Chapter 3
Creating a Program
Getting Started Guide
for HHT
3–9
6. Press
[F2] – MOD_SLT.
7. Assign
1746–IA8
in slot 2: press the
[
↓
]
key twice, then
[ENTER]
. The
following display appears:
Rack 1 = 1746–A4
4–SLOT RACK
Rack 2 = NONE
Rack 3 = NONE
Slot 0 = 1747–L511
CPU–1K USER MEMORY
Slot 2 = 1746–IA8 8–INPUT 100/120 VAC
F1
F2
F3
F4
F5
MOD_RCK MOD_SLT DEL_SLT UND_SLT
8. Call up slot 3 using the cursor key. Press the
[
↓
]
key once.
9. Press
[F2] – MOD_SLT
.
Slot 3 = NONE
appears on the prompt line.
10.Assign
1746–OA8
in slot 3: press the
[
↓
]
seven times. Then press
[ENTER]
. The following display appears:
Rack 1 = 1746–A4
4–SLOT RACK
Rack 2 = NONE
Rack 3 = NONE
Slot 0 = 1747–L511
CPU–1K USER MEMORY
Slot 3 = 1746–OA8 8–OUT(TRI) 100/240 VAC
F1
F2
F3
F4
F5
MOD_RCK MOD_SLT DEL_SLT UND_SLT
Your controller is now fully configured.
11. Press
[ESC]
. This returns you to the display shown below.
File Name:
Prog Name:1000
File Name
Type Size(Instr)
0
System *
1
Reserved *
2
Ladder *
F1
F2
F3
F4
F5
EDT_DAT SEL_PRO EDT_I/O
OFL
CLR_MEM
>
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com