4-30
Configuring the I/O
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Adapter Parameter Settings for SLC 500 Example
These adapter settings were used for the example ladder logic program
in this section.
Creating RSLogix 500 (v7 or higher) Project
To transmit (read and write) data between the controller and drive, you
must create message instructions that allocate data table addresses in
the controller for Logic Command/Status, Reference/Feedback, and
Datalinks. Note that three messages need to be configured. The timeout
Adapter Parameter
Value
Description
01 - [DL From Net 01]
370
Points to drive Par. 370 - [Stop Mode A]
02 - [DL From Net 02]
371
Points to drive Par. 371 - [Stop Mode B]
03 - [DL From Net 03]
535
Points to drive Par. 535 - [Accel Time 1]
04 - [DL From Net 04]
536
Points to drive Par. 536 - [Accel Time 2]
05 - [DL From Net 05]
537
Points to drive Par. 537 - [Decel Time 1]
06 - [DL From Net 06]
538
Points to drive Par. 538 - [Decel Time 2]
07 - [DL From Net 07]
539
Points to drive Par. 539 - [Jog Acc Dec Time]
08 - [DL From Net 08]
556
Points to drive Par. 556 - [Jog Speed 1]
09 - [DL From Net 09]
557
Points to drive Par. 557 - [Jog Speed 2]
10 - [DL From Net 10]
571
Points to drive Par. 571 - [Preset Speed 1]
11 - [DL From Net 11]
572
Points to drive Par. 572 - [Preset Speed 2]
12 - [DL From Net 12]
573
Points to drive Par. 573 - [Preset Speed 3]
13 - [DL From Net 13]
574
Points to drive Par. 574 - [Preset Speed 4]
14 - [DL From Net 14]
575
Points to drive Par. 575 - [Preset Speed 5]
15 - [DL From Net 15]
576
Points to drive Par. 576 - [Preset Speed 6]
16 - [DL From Net 16]
577
Points to drive Par. 577 - [Preset Speed 7]
17 - [DL To Net 01]
370
Points to drive Par. 370 - [Stop Mode A]
18 - [DL To Net 02]
371
Points to drive Par. 371 - [Stop Mode B]
19 - [DL To Net 03]
535
Points to drive Par. 535 - [Accel Time 1]
20 - [DL To Net 04]
536
Points to drive Par. 536 - [Accel Time 2]
21 - [DL To Net 05]
537
Points to drive Par. 537 - [Decel Time 1]
22 - [DL To Net 06]
538
Points to drive Par. 538 - [Decel Time 2]
23 - [DL To Net 07]
539
Points to drive Par. 539 - [Jog Acc Dec Time]
24 - [DL To Net 08]
556
Points to drive Par. 556 - [Jog Speed 1]
25 - [DL To Net 09]
557
Points to drive Par. 557 - [Jog Speed 2]
26 - [DL To Net 10]
571
Points to drive Par. 571 - [Preset Speed 1]
27 - [DL To Net 11]
572
Points to drive Par. 572 - [Preset Speed 2]
28 - [DL To Net 12]
573
Points to drive Par. 573 - [Preset Speed 3]
29 - [DL To Net 13]
574
Points to drive Par. 574 - [Preset Speed 4]
30 - [DL To Net 14]
575
Points to drive Par. 575 - [Preset Speed 5]
31 - [DL To Net 15]
576
Points to drive Par. 576 - [Preset Speed 6]
32 - [DL To Net 16]
577
Points to drive Par. 577 - [Preset Speed 7]
TIP: The [DL From Net xx] parameters are inputs into the drive that
come from controller outputs (for example, data to write to a drive
parameter). The [DL To Net xx] parameters are outputs from the drive
that go to controller inputs (for example, data to read a drive parameter).