PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Appendix
C
Application Notes
For additional application notes, refer to the PowerFlex 700S Adjustable
Frequency AC Drive with Phase II Control - Reference Manual, publication
PFLEX-RM003.
Input Voltage Range/
Tolerance
For Information on …
See Page...
Drive Rating
Nominal Line
Voltage
Nominal Motor
Voltage
Drive Full Power
Range
Drive Operating
Range
200-240
200
200†
200-264
180-264
208
208
208-264
240
230
230-264
380-400
380
380†
380-528
342-528
400
400
400-528
480
460
460-528
500-600
(Frames 1-4 Only)
600
575†
575-660
432-660
500-690
(Frames 5 & 6 Only)
600
575†
575-660
475-759
690
690
690-759
475-759
Drive Full Power Range =
Nominal Motor Voltage to Drive Rated V 10%.
Rated current is available across the entire Drive Full Power
Range
Drive Operating Range =
Lowest† Nominal Motor Voltage - 10% to Drive Rated V
10%.
Drive Output is linearly derated when Actual Line Voltage is less
than the Nominal Motor Voltage