Programming and Parameters
3-71
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
486
Rated Slip Freq
Displays the control slip frequency, determined from
[Motor NP Hertz] and
[Motor NP RPM]. Measured and updated by the autotune procedure. Do not change this
value.
Note: Changed the attributes to allow changing this parameter while the drive is running
for firmware version 3.01.
Units:
Default:
Min/Max:
Scale:
Hz
0.470
0.000/32.000
x 1000
RW 16-bit
Integer
487
Motor NTC Coef
Defines a coefficient used to calculate the rotor temperature from the measured stator
temperature. Used only in Field Oriented Control - 2 (FOC2) mode. See Par
[Motor Ctrl Mode].
Units:
Default:
Min/Max:
%
100
50/200
RW 16-bit
Integer
488 Flux
Current
Specifies the magnetizing current that produces rated flux in the motor in a per unit
(percent representation). Measured by the auto-tune procedure. Do not change this
value.
Units:
Default:
Min/Max:
Scale:
%
30.00
0.00/75.00
x 100
RW 16-bit
Integer
489
Flx CurFdbk (Id)
Displays flux producing (d-axis) current feedback.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
RO Real
490 StatorInductance
Displays the sum of the stator and cable inductances of the motor in per unit (percent
representation), as determined by the auto-tune procedure. Scaled to percent of rated
motor impedance. Do not change this value.
Note: the default value was changed from 8192 to 4096 for firmware version 3.01.
Units:
Default:
Min/Max:
Scale:
%
100.0
0.00/799.99
100 = 4096
RW 16-bit
Integer
491 StatorResistance
Displays the sum of the stator and cable resistances of the motor in per unit (percent
representation), as determined by the auto-tune procedure. Scaled to percent of rated
motor impedance. Do not change this value.
Units:
Default:
Min/Max:
Scale:
%
1.00
0.00/100.00
100 = 8192
RW 16-bit
Integer
492 Leak
Inductance
Displays the sum of the motor stator and rotor leak inductance, and motor cable
inductances in per unit (percent representation), as determined by the auto-tune
procedure. Scaled to percent of rated motor impedance. Do not change this value.
Units:
Default:
Min/Max:
Scale:
%
20.00
0.00/100.00
100 = 8192
RW 16-bit
Integer
493 Leak
Indc
Satur1
Displays the leakage inductance correction for the first overload level as determined by
the autotune procedure.
Units:
Default:
Min/Max:
%
100.00
25.00/100.00
RW 16-bit
Integer
494 Leak
Indc
Satur2
Displays the leakage inductance correction for the first overload level as determined by
the auto-tune procedure.
Units:
Default:
Min/Max:
%
100.00
25.00/100.00
RW 16-bit
Integer
495 Iqs
Command
Displays the torque producing (q-axis) current command.
Units:
Default:
Min/Max:
Scale:
%
0.0
-/+800.0
x 10
RO 16-bit
Integer
496 Ids
Command
Displays the flux producing (d-axis) current command.
Units:
Default:
Min/Max:
Scale:
%
0.0
-/+800.0
x 10
RO 16-bit
Integer
497 Vqs
Command
Displays the command for initiation of voltage on the torque producing axis (q-axis).
Units:
Default:
Min/Max:
Scale:
%
0
-/+200
100 = 8192
RO 16-bit
Integer
498 Vds
Command
Displays the command for initiation of voltage on the flux producing axis (d-axis).
Units:
Default:
Min/Max:
Scale:
%
0
-/+200
100 = 8192
RO 16-bit
Integer
499
Trq CurFdbk (Iq)
Displays torque producing (q-axis) current feedback.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
RO Real
500
Bus Util Limit
Sets the maximum allowed bus voltage utilization for the Motor Control. Do not change
this value. Higher values may result in control instability or over-current faults.
Units:
Default:
Min/Max:
Scale:
%
90.0
0.0/100.0
100 = 8192
RW 16-bit
Integer
501
Torque En Dly
Sets the delay between the time the drive is enabled and the time the Motor Control
applies torque.
Units:
Default:
Min/Max:
Scale:
mSec
100
0/32767
100 = 8192
RW 16-bit
Integer
502 Rotor
Resistance
Displays rotor resistance, as determined by the auto-tune procedure. Scaled to percent of
rated motor impedance. Do not change this value.
Units:
Default:
Min/Max:
Scale:
%
1.00
0.00/100.00
100 = 8192
RW 16-bit
Integer
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype