3-70
Programming and Parameters
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
475
MC FaultTPSelect
Enter or write a value to select the Motor Control (MC) Fault Data displayed in
[MC FaultTP Value]. This parameter should not be changed by the user.
Notes: This parameter was added for firmware version 2.03. The value for option 67 was changed from “HH GateShort” to “MCStatus1” for firmware version 2.04.
Values 68 - 76 were added for firmware version 3.01.
476
MC FaultTP Value
[MC FaultTPSelect]. This parameter should not be
changed by the user.
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
0.0
+/- 2147483648
RO 32-bit
Integer
477 Est
Theta
Delay
Active only in Permanent Magnet motor mode (when
[Motor Ctrl Mode] equals 2
−
“PMag Motor”). Provides a delay for the function that compares the estimated rotor
position and the data from the position sensor.
Units:
Default:
Min/Max:
mSec
10
2/1024
RW 16-bit
Integer
478
VPL Mem Password
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
0
+/-2147483648
RW 32-bit
Integer
479
VPL Mem Address
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
0
0 - 4294967295
RW 32-bit
Integer
480
VPL Mem Data Int
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
32
+/-2147483648
RW 32-bit
Integer
481
VPL Mem Data Flt
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
1.25
RW Real
482
VPL Mem Data Bit
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
1.25
RW 32-bit
Integer
483
VPL Mem Link Int
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max: +/-2147483648
RO 32-bit
Integer
484
VPL Mem Link Flt
Note: This parameter was added for firmware version 2.03.
RO Real
485
Motor Ctrl Mode
Enter a value to select the operating mode for the Motor Control (MC).
•
Value 0 - Field Oriented Control (FOC) is induction motor control with voltage
adaptation.
•
Value 1 - Field Oriented Control 2 (FOC 2) is induction motor control with temperature
adaptation. (This option is used only for motors manufactured by Reliance Electric -
Japan.)
•
Value 2 - Permanent Magnet Motor Control (Pmag Motor) is permanent magnet motor
operation.
•
Value 3 - V/Hz is volts per hertz motor control.
•
Value 4 - Test is the test mode.
Default:
Options:
0 =
0 =
1 =
2 =
“FOC”
“FOC”
3 = “V/Hz”
“FOC 2”
4 = “Test”
“PMag Motor”
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Options:
0 =
IqsRef2
14 = DcBus
29 = DbDuty
43 =
RotorFluxEst
57 = VbusDrop
71 =
HH OverLoad
1 =
Ws
15 = VbusFdbk
30 = VelFdbkEnc0
44 =
Ws2
58 = VdsMax
72 =
HH Precharge
2 =
We
16 = VbusFdbkFltr
31 = VelFdbkEnc1
45 =
BusDropVolts
59 = VbusLow
73 =
HH Fan Alarm
3 =
We2
17 = VbusMemory
32 = VdsCmd2
46 =
RecoverVolts
60 = VbusRising
74 =
HH BusComm
4 =
VdsCmd
18 = Kpwm
33 = VelFdbkOpt1
47 =
TestDtoA0
61 = PreChrgDone
75 =
HH HW Incomp
5 =
VqsCmd
19 = ThetaE
34 = Reserved
48 =
TestDtoA1
62 = FieldWeak
76 =
HH GateShort
6 =
VdsFdbk
20 = FldWeakActiv
35 = Reserved
49 =
TestDtoA2
63 = Reserved
7 =
VqsFdbk
21 = MtrFlxPU
36 = Reserved
50 =
TestDtoA3
64 = DynamBrakeOn
8 =
luFdbk
23 = SlipGainFltr
37 = Reserved
51 =
RideThruActv
65 = Reserved
9 =
IwFdbk
24 = SlipVdsCmd
38 = TorqueEst
52 =
PreChrgReqVp
66 = MCStatusMon
10 = IdsFdbk
25 = MotorVolts
39 = TorqueEstFlt
53 =
Reserved
67 = MCStatus1
11 = IqsFdbk
26 = BusUtil
40 = Reserved
54 =
Reserved
68 = HH OverCurr
12 = IdsCmd
27 = IqsLimit
41 = PowerCalc
55 =
Reserved
69 = HH BusOvrVlt
13 = IqsCmd
28 = VqsIdsCmd
42 = TorqueCmd
56 =
TorqTrimActv
70 = HH Tr Desat