60
Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
Chapter 6
AOP Controller Tags
SI Tags
lists the controller tags for the single input safety relay.
Table 17 - SI Relay Tags (Tag name prefix: ENETRname:I.Relayx_GSR_SI)
Name
Data Type
Definition
IN01
BOOL
IN01 Status - Indicates whether input circuit 1 is ON or OFF.
0 = The input channel is OFF.
1 = The input channel is ON.
ResetRequired
BOOL
Reset Required Indication - This indication turns ON (1) when all monitored input conditions are ON and the safety relay Output is OFF
(0).
CrossLoopOK
BOOL
Cross Loop OK - Indicates whether the safety relay is detecting a cross loop fault on one of the input circuits.
0 = Cross loop fault
1 = No fault
SafetyOutput
BOOL
Safety Output Status – Indicates whether the safety output channels are ON or OFF.
0 = The safety output channels are OFF.
1 = The safety input channels are ON.
RecoverableFault
BOOL
Recoverable Fault Status – Toggles ON (1) for one scan when the SI safety relay has detected an unexpected operation for the
following:
• S12 OpenWire
• S22 OpenWire
• Cross Loop Fault
• Invalid Switch Setting
• Reset Held ON
Toggles back to OFF (0), when the unexpected operation status goes to ON (1).
0 = No fault
1 = Fault
NonRecoverableFault
BOOL
Nonrecoverable Fault Status – Toggles ON (1) for one scan when the safety relay has detected unexpected internal operation or failed
a pulse check. Toggles back to OFF (0), when the nonrecoverable fault tags are assigned a value. See
and
tags for details.
0 = No fault
1 = Fault
S12
BOOL
S12 Status – Indicates whether terminal S12 of circuit IN01 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S22
BOOL
S22 Status – Indicates whether terminal S22 of circuit IN02 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
S34
BOOL
S34 Status – Indicates whether terminal S34 is ON or OFF.
0 = The terminal is OFF.
1 = The terminal is ON.
NonRecoverableFault_A
SINT
Nonrecoverable Fault Processor A – Indicates that Safety Processor A has recorded a nonrecoverable fault. See
for a list of
nonrecoverable fault codes.
NonRecoverableFault_B
SINT
Nonrecoverable Fault Processor B – Indicates that Safety Processor B has recorded a nonrecoverable fault. See
for a list of
nonrecoverable fault codes.
S12OpenWire
BOOL
S12 Open Wire - Indicates S12 open (0) and closed (1) while S22 remained closed (1).
S22OpenWire
BOOL
S22 Open Wire - Indicates S22 open (0) and closed (1) while S12 remained closed (1).
CrossLoopFault
BOOL
Cross Loop Fault – Indicates whether the safety relay has detected a cross loop fault on one of the input circuits.
0 = No fault
1 = Cross loop fault
InvalidSwitchSetting
BOOL
Invalid Switch Settings – Indicates the switch settings changed after power-up of the safety relay.
0 = No fault
1 = Fault
ResetHeldOn
BOOL
Reset Held On Fault – Indicates the reset signal ON (1) for longer than the maximum time of 3000 ms.
0 = No fault
1 = Fault