PowerFlex SCR Bus Supply User Manual
Figure 1.6 1000A Unit Bus Bar and Terminal Locations for Customer Wiring
Table 1.E 1000A Unit Power Connection Specifications
Item Description
Copper Bus Bars
(1)
(1)
Input/output power bus bar connections require the use of either lug type connectors to terminate field-installed
conductors or bus bars.
Recommended Minimum Size
Bus Bar
Wire
➊
AC Line Input
L1, L2, L3
50 x 10 mm (1.97 x 0.39 in.) with
two 14 mm (0.55 in.) diameter
holes for customer terminal
50 x 10 mm
(or 80 x 5 mm)
2 x 240 mm
2
➋
DC Bus
DC+, DC-
60 x 10 mm (2.36 x 0.39 in.) with
two 14 mm (0.55 in.) diameter
holes for customer terminal
60 x 10 mm
(or 100 x 5 mm)
2 x 300 mm
2
➌
Protective Earth PE
M12 x 25 mm (0.98 in.) stud;
torque to 15 N•m (133 lb•in)
Size per NEC or local code
➍
Control Terminal Block
See
DC+
DC-
L1
L2
L3
➋
➊
➍
➌
Summary of Contents for Allen-Bradley PowerFlex SCR
Page 1: ...PowerFlex SCR Bus Supply Firmware Version 1 xxx User Manual...
Page 4: ...soc ii Summary of Changes PowerFlex SCR Bus Supply User Manual Publication 20S UM001G EN P...
Page 6: ...ii Table of Contents PowerFlex SCR Bus Supply User Manual Publication 20S UM001G EN P...
Page 62: ...A 20 Specifications PowerFlex SCR Bus Supply User Manual Publication 20S UM001G EN P Notes...
Page 64: ...B 2 History of Changes PowerFlex SCR Bus Supply User Manual Publication 20S UM001G EN P Notes...
Page 67: ......