
52
Rockwell Automation Publication 750-AT006D-EN-P - January 2022
Chapter 2 Product Features
Lead Lag Filters
Lead-lag filters are represented by the following first order transfer function, where F is the filter bandwidth in units of [Hz] and K is the
filter gain.
The filter is disabled when F = 0 Hz, regardless of the other settings.
The filter has a DC gain of 1, a user-configurable pole (lag) at F, and a user-configurable zero (lead) at F/K. Bode plots with differing gain
settings are shown in
.
10:1005
[u Vel Fb LPF Gain]
Sets the primary velocity feedback filter gain. The
parameter's value sets the mode of the filter and gain of
its first order transfer function. This value affects the
filtering applied to the primary velocity feedback channel
and is only active in Flux Vector motor control modes.
Entering a value of 1 turns off the filter.
• For a low pass filter, enter a value of 0. This is the user default and the
calculated gain value.
• For a lag-lead filter, enter a value between 0 and 1.
• For a lead-lag filter, enter a value greater than 1. This value is applied
when parameter 10:905 [System C/U Sel] is set to 'User Entered' (1).
10:1008
[c AltVelFbLPF BW]
An automatically calculated value for the alternate
velocity feedback low pass filter bandwidth. It is applied
to the drive when
10:905 [System C/U Select] = Calculated (0). It is
calculated as a function of the following parameters and it
affects the DMTC and 10:1010 [Alt Fb GnScale] values.
• 10:407 [Motor Poles] – This parameter is the number of motor poles (p). It
is calculated as follows
p = round (120 x [Motor NP Hertz] / [Motor NP RPM])
• Alternate Encoder Resolution – The total resolution in edge counts per
revolution (EPR) is specified by parameters on the alternate feedback
option card.
– Low-Resolution Example: Resolution = 1024 pulses per revolution * 4
quadrature edge counts per pulse = 4096 EPR (12-bit). The low-
resolution PPR comes directly from a parameter on the option card.
When both A and B channels are selected for an incremental encoder,
the edge count multiplier is 4. This value is the typical and default
setting. When only channel A is selected, then the edge count multiplier
is 2.
– High-Resolution Example: Resolution = 1024 pulses per revolution *
1024 edge counts per pulse = 1,048,576 EPR (20-bit). For high-resolution
devices, the overall resolution choices are 20-bit default or an optional
24-bit when the corresponding configuration bit is selected.
10:1009
[u AltVelFbLPF BW]
Sets the alternate velocity feedback low pass filter bandwidth. It is applied to the drive when parameter 10:905 [System C/U Select] =
User Entered (1).
10:1021
[c AltVelFbLPF Gn]
Displays the calculated value of the alternate velocity
feedback filter gain. This gain value is applied when
parameter 10:905 [System C/U Sel] = 'Calculated' (0). The
'calculated' filter gain is always zero.
• Because this is a Lead Lag Filter, a filter gain of zero will configure the
filter as a Low Pass Filter. See
• This filter determines the amount of filtering applied to the alternate
velocity feedback channel and is only active in Flux Vector motor control
modes.
10:1022
[u AltVelFbLPF Gain]
Sets the alternate velocity feedback filter gain. The
parameter's value sets the mode of the filter and gain of
its first order transfer function. This value determines the
amount of filtering applied to the alternate velocity
feedback channel and is only active in Flux Vector motor
control modes. Entering a value of 1 turns off the filter.
• For a low pass filter, enter a value of 0. This is the user default and the
calculated gain value.
• For a lag-lead filter, enter a value between 0 and 1.
• For a lead-lag filter, enter a value greater than 1. This value is applied
when parameter 10:905 [System C/U Sel] is set to 'User Entered' (1).
10:2154
[c Trq LPF BW]
An automatically calculated value for the torque low pass
filter bandwidth. It is applied to 10:2156 [Trq LPF BW Act]
when 10:905 [System C/U Select] = Calculated (0) and the
adaptive tuning Gain Stabilization function is disabled.
• The value = max (K
VP
, K
OP
) * 5 when the load observer is enabled.
• The value = K
VP
* 5 when the load observer is disabled.
10:2155
[u Trq LPF BW]
Sets the torque low pass filter bandwidth. It is applied to 10:2156 [Trq LPF BW Act] when 10:905 [System C/U Select] = User Entered (1)
and the adaptive tuning Gain Stabilization function is disabled.
Table 19 - Low Pass Filter Parameters (Continued)
Parameter
No.
Parameter Name Description
G s
Ks
2
F
+
s
2
F
+
----------------------------
=
K
s
2
F
K
--------
+
s
2
F
+
------------------------
=