AFE in IP20 2500 MCC Style Enclosure – Installation/Wiring
Chapter 1
Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives,
publication
Interlocked armor is acceptable for shorter cable runs, but continuous welded
armor is preferred.
Best performance is achieved with three spaced ground conductors, but
acceptable performance below 200 Hp is provided by use of one ground
conductor.
Recommended shielded/armored wire is listed in
Table 1 - Recommended Shielded/Armored Wire for AFE in IP20 2500 MCC Style Enclosure
Cable Trays and Conduit
If cable trays or large conduits are used, see the guidelines in Wiring and
Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives,
publication
Select and Verify Control Transformer Voltage
The control transformer in the AFE is used to match the input AC line voltage
of the AFE in an IP20 2500 MCC Style enclosure to the 230V and 120V
control voltage.
Location
Rating/Type
Description
Standard
(option 1)
1000V, 90 °C (194 °F)
XHHW2/RHW-2
Anixter B29528-B29532
Belden 29528-29532
Or equivalent
• Four tinned copper conductors with XLPE insulation.
• Copper braid/aluminum foil combination shield and
tinned copper drain wire.
• PVC jacket.
Standard
(option 2)
Tray rated 1000V, 90 °C (194 °F)
RHH/RHW-2 Anixter
OLFLEX-76
xxx
03
Or equivalent
• Three tinned copper conductors with XLPE insulation.
• Corrugated copper tape with three bare copper grounds
in contact with shield.
• PVC jacket.
Class I & II;
Division I & II
Tray rated 1000V, 90 °C (194 °F)
RHH/RHW-2
Anixter 7VFD-
xxxx
Or equivalent
• Three bare copper conductors with XLPE insulation and
impervious corrugated continuously welded aluminum
armor.
• Black sunlight resistant PVC jacket overall.
• Three copper grounds.
ATTENTION:
To avoid a possible shock hazard that is caused by induced
voltages, unused wires in the conduit must be grounded at both ends. For the
same reason, if a drive that shares a conduit is being serviced or installed, all
drives that use this conduit must be disabled. Disable the drives to help
minimize the possible shock hazard from ‘cross coupled’ motor leads.
Summary of Contents for Allen-Bradley PowerFlex 700AFE
Page 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Page 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Page 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Page 185: ......