88
Rockwell Automation Publication 20Y-TG002C-EN-P - April 2017
Chapter 7
LCL Filter Component Section
2. Disconnect terminal blocks X51 and X53.
3. Lower the front fan sheet metal edge and slide it forward to remove the
alignment studs from their respective holes in the fan frame sheet metal.
4. Slide out the fan assembly.
5. Remove the LCL filter fan DC power supply.
Remove the LCL Filter Fan DC Power Supply on page 85
6. Reinstall the LCL filter fan in reverse order of removal. See
Note the following LCL filter airflow cooling requirements.
Remove the LCL Filter
The procedures to remove the LCL filter are different depending on the
enclosure in which it is installed.
From the IP20 2500 MCC Style Enclosure
To remove the LCL filter from an IP20 2500 MCC enclosure, follow these
steps.
1. Remove power from the AFE.
Remove Power from the AFE on page 37
.
2. Remove the LCL filter protective barriers.
Remove the LCL Filter Protective Barriers and Vented Cover on
3. Remove the airflow plate.
Remove the AFE Airflow Plate on page 46
.
4. Remove the X51 and X53 terminal blocks from the LCL fan assembly.
LCL Filter
Required Airflow
LCL 460
1100 m
3
/hr
LCL 1300
1300 m
3
/hr
X51
X53