Rockwell Automation Publication 20Y-TG002C-EN-P - April 2017
31
Component Test Procedures
Chapter 3
Table 3 - Reverse Biased Diode Tests on Power Structure
If the AFE fails any of these measurements, replace all power modules for each
line phase in the power structure, or the complete power structure. To replace
the components, follow one of these options:
• Contact your local representative to schedule on-site services.
• Contact your local representative to make arrangements to return the
power structure to the factory for repair by Remanufacturing Services.
• For an AFE not covered under factory warranty, a customer has the
option of repairing the power structure using procedures that are
described in this manual.
Check the Fiber-optic
Connections
Damaged or improperly connected fiber-optic cables can cause apparent gate
driver board malfunctions. For fiber-optic cable connections, see
, and
The check the fiber-optic connection, follow these steps.
1. Remove power from the AFE.
Remove Power from the AFE on page 37
.
2. If present, remove the protective barriers.
Remove AFE Protective Barriers on page 44
.
3. Remove the protective front covers and terminal covers from the power
Remove Protective Covers from the Power Structure on page 47
.
4. Locate the three gate driver boards on the front of the power structure
(right-side AFE enclosure).
Meter Leads
)
Nominal Meter Reading
+
-
U/T1
DC-
1
Meter displays ‘.0L’ (zero load)
V/T2
DC-
W/T3
DC-
DC+
U/T1
2
DC+
V/T2
DC+
W/T3