3-32
Programming and Parameters
D
YNAMIC CONTR
O
L
Rest
ar
t Modes
179
[Sleep-Wake Ref]
Selects the source of the input controlling
the Sleep-Wake function.
Default:
Options:
2
1
2
“Analog In 2”
“Analog In 1”
“Analog In 2”
180
[Wake Level]
Defines the analog input level that will
start the drive.
Default:
Min/Max:
Units:
6.000 mA, 6.000 Volts
[Sleep Level]/20.000 mA
10.000 Volts
0.001 mA
0.001 Volts
181
[Wake Time]
Defines the amount of time at or above
[Wake Level] before a Start is issued.
Default:
Min/Max:
Units:
0.0 Secs
0.0/1000.0 Secs
0.1 Secs
182
[Sleep Level]
Defines the analog input level that will
stop the drive.
Default:
Min/Max:
Units:
5.000 mA, 5.000 Volts
4.000 mA/[Wake Level]
0.000 Volts/[Wake Level]
0.001 mA
0.001 Volts
183
[Sleep Time]
Defines the amount of time at or below
[Sleep Level] before a Stop is issued.
Default:
Min/Max:
Units:
0.0 Secs
0.0/1000.0 Secs
0.1 Secs
P
o
wer Lo
ss
177
[Gnd Warn Level]
Sets the level at which a ground warning
fault will occur. Configure with [Alarm
Config 1].
Default:
Min/Max:
Units:
3.0 Amps
1.0/5.0 Amps
0.1 Amps
184
[Power Loss Mode]
Sets the reaction to a loss of input power.
Power loss is recognized when:
•
DC bus voltage is
≤
73% of [DC Bus
Memory] and [Power Loss Mode] is
set to “Coast”.
•
DC bus voltage is
≤
82% of [DC Bus
Memory] and [Power Loss Mode] is
set to “Decel”.
Default:
Options:
0
0
1
2
3
4
“Coast”
“Coast”
“Decel”
“Continue”
“Coast Input”
“Decel Input”
185
[Power Loss Time]
Sets the time that the drive will remain in
power loss mode before a fault is issued.
Default:
Min/Max:
Units:
0.5 Secs
0.0/60.0 Secs
0.1 Secs
Fi
le
Gr
ou
p
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Relate
d