
130
Rockwell Automation Publication 520-UM001K-EN-E - August 2021
Chapter 3 Programming and Parameters
Advanced Program Group
(continued)
A531 [Start Boost]
Related Parameter(s):
Sets the boost voltage (% of
[Motor NP Volts]) and redefines the V/Hz curve when
[Boost Select] = 0 “Custom V/Hz” and
[Torque Perf Mode] = 0 “V/Hz”.
Values
Default:
2.5%
Min/Max:
0.0/25.0%
Display:
0.1%
Frequency
Voltage
[Break Frequency]
[Motor NP Hertz]
[Maximum Freq]
[Start Boost]
[Motor NP Volts]
[Maximum Voltage]
[Break Voltage]
[Minimum Freq]
A532 [Break Voltage]
Related Parameter(s):
Sets the voltage (in percent of [Base Frequency]) at the
[Break Frequency] if
[Boost Select] is set to 0 “Custom V/Hz”.
Values
Default:
25.0%
Min/Max:
0.0/100.0%
Display:
0.1%
A533 [Break Frequency]
Related Parameter(s):
,
Sets the frequency where
[Boost Select] is set to 0 “Custom V/Hz”.
Values
Default:
15.0 Hz
Min/Max:
0.0/500.0 Hz
Display:
0.1 Hz
A534 [Maximum Voltage]
Related Parameter(s):
Sets the highest voltage the drive outputs.
Values
Default:
Drive Rated Volts
Min:
10V AC (on 230V AC Drives); 20V AC (on 460V AC Drives); 25V AC (on 600V AC Drives)
Max:
255V AC (on 230V AC Drives); 510V AC (on 460V AC Drives); 637.5V AC (on 600V AC Drives)
Display:
1V AC
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...