Advanced Program Group
(continued)
A109 [Anlg Out Setpt]
Related Parameter(s):
When A065 [Analog Out Sel] is set to option 18, 19 or 20, this parameter sets the percentage of
analog output desired.
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
A110 [Anlg In 0-10V Lo]
,
,
Sets the analog input level that corresponds to P034 [Minimum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value larger than A111 [Anlg In 0-10V Hi].
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
0
P035 [Maximum Freq]
P034 [Minimum Freq]
A110 [Anlg In 0-10V Lo]
A111 [Anlg In 0-10V Hi]
0
Speed Reference
A111 [Anlg In 0-10V Hi]
Related Parameter(s):
,
,
Sets the analog input level that corresponds to P035 [Maximum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value smaller than A110 [Anlg In 0-10V Lo].
Values
Default:
100.0%
Min/Max:
0.0/100.0%
Display:
0.1%
A112 [Anlg In4-20mA Lo]
Related Parameter(s):
,
Sets the analog input level that corresponds to P034 [Minimum Freq] if a 4-20mA input is used by
[Speed Reference].
Analog inversion can be accomplished by setting this value larger than A113 [Anlg In4-20mA Hi].
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%