3-4
Programming and Parameters
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Display Group
(continued)
d006 [Drive Status]
Related Parameter(s):
Present operating condition of the drive.
Values
Default:
Read Only
Min/Max:
0/1
Display:
1
1 = Condition True, 0 = Condition False
Running
Bit 0
Forward
Bit 1
Accelerating
Bit 2
Decelerating
Bit 3
d007 [Fault 1 Code]
d008 [Fault 2 Code]
d009 [Fault 3 Code]
A code that represents a drive fault. The codes will appear in these parameters in the order they occur
(
[Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once.
Refer to
for fault code descriptions.
Values
Default:
Read Only
Min/Max:
F2/F122
Display:
F1
d010 [Process Display]
Related Parameter(s):
,
32 bit parameter.
The output frequency scaled by
[Process Factor].
Values
Default:
Read Only
Min/Max:
0.00/9999
Display:
0.01 – 1
32
Output
Freq
Process
Factor
Process
Display
=
x
22B-UM001.book Page 4 Tuesday, May 30, 2017 5:22 PM