Total Resistance Values
Table 15 - 230V AC Input Drives
Table 16 - 460V AC Input Drives
3. Seal the TA potentiometer in place using RV (silicon).
4. Continue with Install the Pulse Transformer and Switching Power
Supply Boards on page
.
Configure a Pulse Transformer Board FIR2-xx Rev. “N” and Higher
Set DIP switches S3 and S4, located at the bottom right corner of the pulse
transformer board (shown below), to the correct settings based on the
appropriate table below.
Drive Current
Rating Code
DC
Amps
AC Line
Amps
Hp
Set RTA Value Using TA
Potentiometer (Ohms)
146
146
119
40
12.575
180
180
147
50
10.2
218
218
178
60
8.422
265
265
217
75
6.928
360
360
294
100
5.1
434
434
355
125
4.23
Drive Current
Rating Code
DC
Amps
AC Line
Amps
Hp
Set RTA Value Using TA
Potentiometer (Ohms)
167
167
136.4
100
10.994
207
207
169.1
125
8.87
250
250
204.3
150
7.344
330
330
269.6
200
5.564
412
412
336.6
250
4.456
XSW1
XI2CA
X3
XP
TR2
TR1
XR
X4
XY
XCD_IO
TO5
TO3
TO6
TO1
TO4
TO2
KGO1
KGO4
KGO2
KGO5
KGO3
KGO6
T5
T3
T6
T1
T2
KG1
KG4
KG2
KG5
KG3
KG6
XCT
C
U
PE
PE1
V
XTA
XM
D
78 79 35 36 75 76 U2 V2
W
S3
S4
1U2 1V2
T4
1
D
79 35 36 75 76 U2 V2
S3
S4
1
Dip switches S3 and S4 are located at the bottom,
right corner of the board.