Install the PanelView 5510 Terminal
Panel Guidelines
The terminals are panel-mounted devices that mount in the door or wall of a
NEMA, UL Type, or IP rated enclosure:
• Enclosure panels must meet the panel thickness requirements in
• The material strength and stiffness of the panel must be sufficient to hold
the terminal and maintain an appropriate seal against water and dust.
• The panel surface must be flat and free of imperfections to maintain an
adequate seal and NEMA, UL Type, or IP ratings.
Panel Cutout Dimensions
Use the template that is shipped with your terminal to mark the cutout
dimensions.
Table 11 - PanelView 5510 - Panel Cutout Dimensions
Terminal Size
Input Type
Height, mm (in.)
Width, mm (in.)
6.5-in.
Keypad and touch
142 (5.59)
237 (9.33)
Touch
142 (5.59)
184 (7.24)
7-in.
Touch
150 (5.9)
210 (8.25)
9-in.
Touch
162 (6.38)
252 (9.92)
10.4-in.
Keypad and touch
224 (8.82)
335 (13.19)
Touch 224
(8.82)
269
(10.59)
12.1-in.
Touch
218 (8.58)
312 (12.28)
15-in.
Keypad and touch
290 (11.42)
418 (16.46)
Touch
290 (11.42)
353 (13.90)
19-in.
Touch
383 (15.08)
457 (17.99)
Summary of Contents for Allen-Bradley PanelView 5510 Series
Page 6: ...6 Rockwell Automation Publication 2715P UM001C EN P March 2019 Table of Contents Notes...
Page 10: ...10 Rockwell Automation Publication 2715P UM001C EN P March 2019 Preface Notes...
Page 108: ...108 Rockwell Automation Publication 2715P UM001C EN P March 2019 Index Notes...
Page 109: ...Rockwell Automation Publication 2715P UM001C EN P March 2019 109 Index Notes...
Page 110: ...110 Rockwell Automation Publication 2715P UM001C EN P March 2019 Index Notes...
Page 111: ......