218
Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 10
Troubleshooting the Drive
Board Replacement,
Firmware Setup Procedures
This section defines drive firmware setup procedures that are required after a
LiquiFlo 2.0 drive board is replaced. If a board is not mentioned in this section,
then firmware setup is not required for that board.
Clearing Drive Faults
1.
An Operator Interface Module (OIM) can be used to clear faults if an
OIM is available:
a. Plug the OIM into the appropriate connector on the Communications
Interface Board (LiquiFlo 2.0 Frame 3), or Control Board (LiquiFlo 2.0
Frame 4).
b. The status area at the top of the OIM display should be
Faulted
, and
the drive status LED (inverter status LED on the Communications
Interface Board [for LiquiFlo 2.0 Frame 3] or the Combined Control
Board [for LiquiFlo 2.0 Frame 4]), should be blinking red.
c. Go to inverter parameter 276 (Logic Mask) and set all the bits to 1.
d. Go to inverter parameter 283 (Fault Clr Mask) and set all the bits to 1.
e. Press the stop key on the OIM. This key is normally colored red and is
marked
0
.
2.
If the fault still exists, remove power to the entire drive, wait 5 minutes, and
then restore power.
LiquiFlo 2.0 Frame 3 Firmware Setup Procedures
Inverter Control Board
1.
Reset all inverter parameters to defaults by setting inverter parameter 197
(Reset to Defalts) to 1. The value of parameter 197 (Reset to Defalts)
returns to 0 immediately after 1 is written to memory. This action should
clear faults 100 (Parameter Checksum) and 107 (Replaced MCB-PB).
2.
The reset to defaults operation normally causes drive fault 48 (Params
Defaulted) to occur. This fault is for information only, and should be
cleared. See
Clearing Drive Faults on page 218
. If drive is still faulted after
this attempt is made, troubleshoot on the basis of the current fault.
3.
Reprogram all drive parameters.
IMPORTANT
The procedure for recovering from a board replacement may cause a drive fault.
The appropriate response to many, although not all, of these faults is to clear
the fault and continue the procedure. This section gives details on how to clear
faults.
IMPORTANT
If drive fault 106 (Incompat MCB-PB) occurs after replacing board or at any
other point during this procedure, then the new inverter control board is
incompatible with the older inverter power interface board. Replace the older
inverter power interface board.
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......