Publication 2094-UM001A-EN-P — September 2006
Connecting the Kinetix 6000 Drive System
87
Wiring the Control Power Output (CPL) Connector
Line Interface Module (CPL connector)
Control Power Output (CPL) Connector
2094-AL
xx
S, -BL
xx
S, -XL75S-C
x
Control Power Output (CPL) Connector
2094-AL09 and -BL02
CTRL
2
CTRL
1
1 2
Line Interface Module, Top
V
iew
(2094-XL75
S
-C
x
is shown)
CPL Pin
Signal
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
Nm (lb-in)
1
CTRL 1
0.2-4.0
(24-10)
7.0
(0.28)
0.5 - 0.6
(4.4 - 5.3)
2
CTRL 2
CPL Pin
Signal
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
Nm (lb-in)
2
L1
2.5
(14)
10.0
(0.38)
0.5 - 0.6
(4.4 - 5.3)
1
L2/N