background image

GuardPLC Digital Input/Output Module     

13

Rockwell Automation Publication 1753-IN003C-EN-P - June 2010

Status Indicators

Indicator

State

Description

24V DC

On

24V DC operating voltage present.

Off

No operating voltage.

RUN

On

This is the normal status of the controller.
A routine, which has been loaded into the controller, is executed.
The controller processes input and output signals, carries out communication, and 
performs hardware and software tests.

Flashing

The controller is in STOP mode and is not executing a routine.
All system outputs are reset.
STOP mode can be triggered by setting the 

Emergency stop

 system variable to TRUE 

in the routine, or by direct command from the programming software.

Off

The controller is in ERROR_STOP mode (see ERROR).

ERROR

On

A hardware error has been detected by the controller. The controller goes to 
ERROR_STOP mode and the execution of the routine is halted. Hardware errors 
are errors in the controller, errors in one or more of the digital input and output 
modules, or errors in the counters.

A software error in the operating system has been detected by the controller.

The watchdog has reported an error due to exceeded cycle time.

All system outputs will be reset and the controller ceases all hardware and 
software tests. The controller can only be restarted by a command from the 
programming software.

Off

No errors are detected.

PROGress

On

The upload of a new controller configuration is in progress.

Flashing

The upload of a new operating system into the nonvolatile ROM is in progress.

Off

No upload of controller configuration or operating system in progress.

FORCE

On

The controller is executing a routine (RUN) and FORCE mode is activated by the user.

Flashing

The controller is in STOP mode, but Forcing has been initiated and will be activated 
when the controller is started. 

Off

Forcing is OFF.

FAULT

On

The routine (logic) has caused an error.

The controller configuration is faulty.

The upload of a new operating system was not successful and the operating 
system is corrupted.

Flashing

An error has occurred during a nonvolatile ROM write cycle. 
One or more I/O errors have occurred.

Off

None of the above errors has occurred.

OSL

Flashing

Emergency 

O

perating 

S

ystem 

L

oader is active.

BL

Flashing

B

oot 

L

oader unable to load operating system or unable to start COMM operating 

system loader.

Module status can be interrogated through the programming software. For more information, refer to the 
GuardPLC System User Manual, publication 

1753-UM001

.

Summary of Contents for Allen-Bradley GuardPLC 1753-IB20XOB8

Page 1: ...8 Topic Page Important User Information 2 About the Module 3 General Safety 3 Install the Module 4 Mount the Module 5 Ground the Module 5 Wire the Module 6 Make Connections for Safety related Communication 12 Reset Push Button 12 Status Indicators 13 Specifications 14 Additional Resources 18 ...

Page 2: ...particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automati...

Page 3: ...on of the system and shall be trained in using the system ATTENTION This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment Touch a grounded object to discharge static potential Wear an approved wrist strap grounding device Do not touch connectors or pins on component boards Do not tou...

Page 4: ...d disturbances This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The enclosure must have suitable flame retardant properties to prevent or minimize the spread of flame compl...

Page 5: ...n on proper grounding guidelines refer to the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 IMPORTANT For effective cooling mount the module following these guidelines Mount the module horizontally Provide a gap of at least 100 mm 3 94 in above and below the module Select a location where air flows freely or use an additional fan Do not mount the module over a heating ...

Page 6: ...ons A PELV supply has the same rating and is connected to protected earth The supply voltage is connected via a 4 pin connector that accommodates wire sizes up to 2 5 mm2 14 AWG You need to connect only one wire to L and one wire to L Both L and L terminals are internally connected so you can daisy chain 24V DC power from the module to other devices in the panel by using the remaining terminal IMP...

Page 7: ... 9 10 11 12 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 24V DC RUN 24 V DC PROG ERROR FAULT FORCE BL OSL GuardPLC Ethernet 10 100 BaseT 1 2 1753 IB20OXB8 20 DC Inputs 8 DC Outputs 1 LS L D1 2 3 4 13 14 15 16 17 18 13 14 15 16 23 24 L L L L 24V DC 24V DC Power Supply COM Connection of Voltage Supply to Input Device L L L L 1 LS LS LS LS LS L D1 2 3 4 13 14 15 16 17 18 5 L D1 6 7 8 19 20 2...

Page 8: ... connected to these terminals Terminal Number Designation Function 13 LS Sensor supply for inputs 1 4 14 1 Digital input 1 15 2 Digital input 2 16 3 Digital input 3 17 4 Digital input 4 18 L Reference pole L L L L 1 LS LS LS LS LS L D1 2 3 4 13 14 15 16 17 18 5 L D1 6 7 8 19 20 21 22 23 24 9 L D1 10 11 12 25 26 27 28 29 30 13 L D1 14 15 16 31 32 33 34 35 36 17 L D1 18 19 20 37 38 39 40 41 42 19 20...

Page 9: ...nput 6 22 7 Digital input 7 23 8 Digital input 8 24 L Reference pole 25 LS Sensor supply for inputs 9 12 26 9 Digital input 9 27 10 Digital input 10 28 11 Digital input 11 29 12 Digital input 12 30 L Reference pole 31 LS Sensor supply for inputs 13 16 32 13 Digital input 13 33 14 Digital input 14 34 15 Digital input 15 35 16 Digital input 16 36 L Reference pole 37 LS Sensor supply for inputs 17 20...

Page 10: ...s that is when one of the E stop off switches is pressed in the example above Safety related Digital Outputs The module has eight digital outputs DO1 DO8 whose status is indicated via status indicators An output is in a safe state when it is de energized If a fault occurs all outputs are turned off Outputs 1 3 and 5 7 can have a load of 0 5 A at an ambient temperature of 60 C 140 F Outputs 4 and 8...

Page 11: ...t 2 4 3 Digital output 3 5 4 Digital output 4 6 L Reference pole 7 L Reference pole 8 5 Digital output 5 9 6 Digital output 6 10 7 Digital output 7 11 8 Digital output 8 12 L Reference pole TIP Inductive loads can be connected without a protection diode on the load However Rockwell Automation strongly recommends that a protection diode be fitted directly to the load to suppress any interference vo...

Page 12: ...t via the push button is necessary under the following conditions You forget the password to go online via the programming software You are unable to determine the IP address and SRS of the controller The push button is accessible through a small round hole at the top of the housing approximately 4 5 cm 1 6 2 0 in from the left rim and recessed approximately 9 5 mm 0 375 in To reset press and hold...

Page 13: ...r due to exceeded cycle time All system outputs will be reset and the controller ceases all hardware and software tests The controller can only be restarted by a command from the programming software Off No errors are detected PROGress On The upload of a new controller configuration is in progress Flashing The upload of a new operating system into the nonvolatile ROM is in progress Off No upload o...

Page 14: ...per wire rated at 75 C 167 F or greater with 1 2 mm 3 64 in insulation max Ethernet RJ45 connector according to IEC 60603 7 2 or 4 pair Category 5e minimum cable according to TIA 568 B 1 or Category 5 cable according to ISO IEC 24702 Wire type Shielded on Ethernet Terminal Block Torque 0 51 N m 4 5 lb in Fuse external 24V DC power 10 A time lag Pilot Duty Rating Not rated Response time 10 ms Batte...

Page 15: ...channels 1 3 and 5 7 4 A for 10 ms 1Hz channels 4 and 8 Current load min 2 mA per channel Internal voltage drop 2V max 2 A Leakage current with 0 signal 1 mA max 2V Total output current 7 A max with exceeding shut down of all outputs with cyclic reconnecting Response overload Shut down of the concerned output with cyclic reconnecting 1 Use this Conductor Category information for planning conductor...

Page 16: ...EC 60068 2 27 Test Ea unpackaged shock 15 g Relative humidity IEC 60068 2 30 Test Db unpackaged damp heat 10 95 noncondensing Emissions CISPR 11 Group 1 Class A ESD Immunity IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF Immunity IEC 61000 4 3 10V m with 1kHz sine wave 80 AM from 80 MHz 2000 MHz 1 V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B Immunity IEC 61000 4 4...

Page 17: ...t certified for US and Canada See UL File E65584 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A B C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Functional Safety Certifi...

Page 18: ...LC Controller Systems Safety Reference Manual publication 1753 RM002 Detailed information regarding the safety certification of the GuardPLC System GuardPLC Controller Systems User Manual publication 1753 UM001 Detailed information on installing wiring configuring operating maintaining and troubleshooting GuardPLC systems Using RSLogix Guard PLUS Software with GuardPLC Controllers Programming Manu...

Page 19: ...GuardPLC Digital Input Output Module 19 Rockwell Automation Publication 1753 IN003C EN P June 2010 ...

Page 20: ...is manual You can also contact a special Customer Support number for initial help in getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures Documentation Feedback...

Reviews: