![Rockwell Automation Allen-Bradley G Series User Manual Download Page 38](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-g-series/allen-bradley-g-series_user-manual_1475408038.webp)
38
Rockwell Automation Publication 1502-UM060A-EN-P - October 2020
Chapter 4 Maintenance
Figure 22 - Access to Coils
2. Remove the retaining ring from the core of the coil you wish to replace as
shown in
3. Loosen the auxiliary assembly retaining bolt and slide the assembly and
the coils forward and out of the contactor as shown in
Figure 23 - Coil Removal
4. Disconnect the coil leads (take note of their location). Connect the leads
of the new coil making sure that all metal-oxide varistors (MOVs) and/or
diodes are secure. See the appropriate wiring diagram in this manual for
further control wiring details (
).
5. Slide the new coil into position and install the retaining ring on the core.
Install the auxiliary assembly leaving the retaining bolt loose for
adjustment later. See the Auxiliary Contact Setup Procedure (
determining the position of the auxiliary assembly.
Grade 5 (5/16 in. Hardware)
to mount return
spring actuator plate
Grade 5 (5/16 in. Hardware)
to mount armature plate
Auxiliary Actuator
Armature Plate
Armature Stop Bracket
Return Spring Actuator Plate
Stop Bracket Bolts
Auxiliary Assembly
Retaining Bolt
Operating Coil
Operating Coil
Retaining Ring
Auxiliary Assembly