Installation and Wiring
Figure 35 - E300 Expansion Power Supply Wiring Diagram
Grounding
The following grounding recommendations are provided to help ensure EMC
requirements during installation
.
•
The earth ground terminal of the E300 Electronic Overload Relay shall be
connected to a solid earth ground via a low-impedance connection.
•
Wire the green shield wire of the Cat. No. 193-ECM-ETR into the earth
ground terminal of the E300 control module.
•
Installations employing an external ground fault sensor shall ground the
cable shield at the sensor with no connection made at the E300 Electronic
Overload Relay.
•
The PTC thermistor cable shield shall be grounded at the E300 Electronic
Overload Relay with no connection made at the opposite end.
Short-Circuit Ratings
The E300 Electronic Overload Relay is suitable for use on circuits capable of
delivering not more than the RMS symmetrical amperes listed in the following
tables.
Table 6 - Standard Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1
A1 A2
Source
+
-
Overload Relay with Sensing Module Cat. No.
Max. Available Fault Current [A]
Maximum Voltage [V]
193-ESM-___-30A-C23
5,000
600
193-ESM-___-30A-C55
193-ESM-___-30A-E3T
193-ESM-___-30A-P
193-ESM-___-30A-T
193-ESM-VIG-30A-CT
592-ESM-___-30A-S2
193-ESM-___-60A-C55
193-ESM-___-60A-E3T
193-ESM-___-60A-P
193-ESM-___-60A-T
592-ESM-___-60A-S2
193-ESM-___-100A-C97
10,000
600
193-ESM-___-100A-E3T
193-ESM-___-100A-T
592-ESM-___-100A-S3
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......