Metering and Diagnostics
Chapter 8
Table 481 - Analog Trip History Mask (Parameter 143)
Warning History
When the E300 Electronic Overload Relay issue a warning, the reason for the
warning is recorded into the Warning History.
available for the warning history records.
Table 482 - Warning History Codes
Bit
Function
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
X
Analog Module 1 - Input Channel 00 Trip
X
Analog Module 1 - Input Channel 01 Trip
X
Analog Module 1 - Input Channel 02 Trip
X
Analog Module 2 - Input Channel 00 Trip
X
Analog Module 2 - Input Channel 01 Trip
X
Analog Module 2 - Input Channel 02 Trip
X
Analog Module 3 - Input Channel 00 Trip
X
Analog Module 3 - Input Channel 01 Trip
X
Analog Module 3 - Input Channel 02 Trip
X
Analog Module 4 - Input Channel 00 Trip
X
Analog Module 4 - Input Channel 01 Trip
X
Analog Module 4 - Input Channel 02 Trip
Warning History Code Description
0
No Warning Conditions Detected
1
Approaching a motor current overload condition
3
Power conductor or motor winding is shorting to ground
5
Motor current has exceed the programmed jam warning level
6
Motor current has fallen below normal operating levels
7
Phase to phase current imbalance detected
8
L1 Current was below L1 Undercurrent Warning Level
9
L2 Current was below L2 Undercurrent Warning Level
10
L3 Current was below L3 Undercurrent Warning Level
11
L1 Current was over L1 Overcurrent Warning Level
12
L2 Current was over L2 Overcurrent Warning Level
13
L3 Current was over L3 Overcurrent Warning Level
14
L1 Current Lost for longer than the L1 Loss Trip Delay
15
L2 Current Lost for longer than the L2 Loss Trip Delay
16
L3 Current Lost for longer than the L3 Loss Trip Delay
17
Line to Line Under-Voltage condition detected
18
Line to Line Over-Voltage condition detected
19
Phase to phase voltage imbalance detected
20
The unit detects the supply voltage phases are rotated
21
Line voltage frequency is below the warning level
22
Line voltage frequency has exceeded warning level
33
Total Real Power (kW) is below warning level
34
Total Real Power (kW) has exceeded warning level
35
Under Reactive Power Consumed (+kVAR) condition detected
36
Over Reactive Power Consumed (+kVAR) condition detected
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......